67
Instruction Manual
AFQevo
●
Min current
The minimum load current to start the active filter is configured with this parameter. The
AFQe-
vo
will stop when the load current is below the entered value and will start when it is higher.
Range of values:
Minimum value:
0 A
Maximum value:
5000 A
● Current limit
This parameter allows the maximum power of the active filter to be limited. The value is config
-
ured as a percentage with respect to the device's nominal power.
Range of values:
Minimum value:
20%
Maximum value:
100%
● Cos ɸ
This parameter allows select the cos ɸ that the active filter must obtain.
Range of values:
0.7 ... -0.7
Press the
key to access the next configuration step
Press the
key to access the main screen of the device without saving the configuration
values.
7.7.- TRANSFORMER CONFIGURATION
Note:
This screen is not visible on the “
slave
” devices.
The transformers that will be installed with the device are configured in this screen,
Figure 70:
Configuration screen: Transformer configuration.