54
AFQevo
Instruction Manual
6.13.- ALARMS
Note:
This screen is not visible on the “
slave
” devices.
In this screen,
, the alarms that have occurred are shown.
Figure 53: Alarms�
A brief description of the alarm is displayed on the screen, as well as the date and time at which
it occurred.
Press the
key to delete the alarm log.
shows the messages that could appear on the device.
If the cause of the alarm disappears, the device will be reconnected automatically.
If the same alarm is triggered 5 times during a 1-hour period, the automatic device reconnection
function will be disabled.
The
key rearms the device if the cause of the alarm has disappeared or has been
resolved.
Use the
and
keys to navigate through the different display screens.
Table 22:Alarm messages�
Alarm messages
Overcurrent L1/L2/L3
Description
The
AFQevo
current is too high.
Corrective
action
This alarm may be associated with transients and noise in the power supply voltage. Check the
quality of the power supply voltage. If it continues, contact the Technical Assistance Service
Main overvoltage L1/L2/L3
Description
The main voltage is too high.
Corrective
action
This alarm may be associated with transients and noise in the power supply voltage, or with
incorrect main voltage values. Check the configuration. Check the quality of the power supply
voltage. If it continues, contact the Technical Assistance Service
High temp IGBT
Description
The temperature of the power module is very high.
Corrective
action
Check that the fans are working. Clean or replace them if necessary. If it continues, contact the
Technical Assistance Service