65
Instruction Manual
AFQevo
The phase balancing option in
AFQe-3Wx-xxxx
works in unbalances produced
by loads connected between phases in three-phase mains without neutral. The
AFQe-3Wx-xxxx
does not compensate unbalances produced by single-phase
loads connected between phase and neutral.
Priority
Enable this option so that the device prioritises the functions in case of filter current saturation
due to overload:
With the function
enabled
, the current balancing between phases and the reactive current com-
pensation is prioritised over the harmonic filtering.
With the function
disabled
, priority is given to the current harmonic filtering and power factor
correction and overload balancing are penalised.
Table 24: Order of priorities
Priority
Order of priorities function
Disabled
Enabled
+
Harmonic filtering
Phase balancing
Power factor correction
-
Phase balancing
Power factor correction
Harmonic filtering
Reactive
Enable this function so that the device compensates the reactive energy or corrects the dis-
placement power factor, cos Φ.
Press the
key to access the next configuration step
Press the
key to access the main screen of the device without saving the configuration
values