82
AFQevo
Instruction Manual
10�- MAINTENANCE
The
AFQevo
active filter requires minimum preventive maintenance.
It is recommended to follow the notes described in this chapter to avoid prema-
ture damage to the device's components.
shows the maintenance jobs with their respective time intervals.
Table 41:
Active filter maintenance.
Description
Interval
Standard maintenance
12 months
Replacement of the cooling fans
40000 h
The device controls the maintenance intervals and shows the
symbol on the main screen
of the device if maintenance is required.
The warnings screen, “
” describes the type of maintenance procedures that
must be carried out.
Note:
The time intervals of the maintenance operations can vary depending on the device's
operating conditions and environmental factors.
Follow the safety instructions in the
section before car-
rying out any maintenance on the
AFQevo
filters.
Failure to follow these instructions may result in injury or even death�
Certain components in the device can reach high temperatures� Allow the
device to cool down before performing any maintenance operations�
10.1.- STANDARD MAINTENANCE
Perform maintenance every 6 to 12 months, depending on the level of environ-
mental dirt and operation of the device.
The device will indicate that the maintenance procedures must be carried out
every 12 months.
For an installation with devices in parallel, standard maintenance must be per-
formed on all devices at the same time.