Digital Power Meter 66203/66204 User’s Manual
2-2
Accuracy
Requirements
1. Temperature:
23°C±5°C
2. Humidity:
80%RH.
3. Input waveform: Sine wave
4. Power factor: 1.
5. Warm-up
time:
≧
30 minutes.
6. Connect the power cord to a three-prong power outlet with proper grounding.
Voltage / Harmonics Specifications
DC, 10Hz-1kHz
1kHz-10kHz
Temperature Coefficient
% r % range
(ppm of r ppm of range) /°C
0.1+0.08 (0.1+0.05*kHz)+0.08
120+150
Note:
1. The temperature coefficient accuracy is used for the situation when the
ambient is beyond the accuracy-permitted temperature. This accuracy should
be added into the voltage accuracy written above.
2. The permitted frequency of voltage harmonics is up to 6 kHz.
Current / Harmonics Specifications
DC, 10Hz-1kHz
1kHz-10kHz
Temperature Coefficient
% r % range
(ppm of r % of range) /°C
0.1+0.1 (0.1+0.05*kHz)+0.1
120+0.05
Note:
1. When measuring current, the voltage of 1/10 larger than the voltage range has
to be inputted for frequency generation, voltage calculation and current
measurement.
2. The temperature coefficient accuracy is used for the situation when the
ambient is beyond the accuracy-permitted temperature. This accuracy should
be added into the voltage accuracy and the current accuracy written above.
3. The power meter should be in a thermally stable environment with power
turned-on for at least 30 minutes before performing auto-calibration (Cali).
4. The permitted frequency of current harmonics is up to 6 kHz.
Specifications of the External Current Sensor input
DC, 10Hz-1kHz
1kHz-10kHz
Temperature Coefficient
% r % range
(ppm of r % of range) /°C
0.1+0.1 (0.1+0.05*kHz)+0.1
120+0.05
Note:
Add DC values 50uV to accuracies for the external current sensor range.
Active Power Specifications
DC 47Hz-63Hz 10Hz-1kHz
1kHz-10kHz
% % range
0.1+0.1 0.1+0.1
0.1+0.18
(0.1+0.1*kHz)+0.18
Note:
1. The temperature coefficient is same as the temperature coefficient for voltage
and current.
2. Influence of power factor: Add the power reading × (0.0015/PF*Hz)% when
0<PF<1
Power Factor Specifications
Range
Range : 0.0000-1.0000
Accuracy 0.001+(15ppm/PF)*Hz
Summary of Contents for 66203
Page 1: ...Digital Power Meter 66203 66204 User s Manual...
Page 2: ......
Page 3: ...Digital Power Meter 66203 66204 User s Manual Version 1 0 March 2014...
Page 8: ...vi...
Page 12: ......
Page 22: ......
Page 26: ......
Page 76: ......
Page 126: ......
Page 130: ......
Page 132: ......
Page 136: ......
Page 144: ......