Remote Operation
5-33
Query Example:
ADV:TIM:RISE?
ADV:TIM:RISE? MAX
ADV:TIM:RISE? MIN
ADVance:TIMing:TOUT
Type:
Channel-Specific
Description:
Set timeout for Timing mode.
Setting Syntax:
ADVance:TIMing:TOUT<space><NRf+>[suffix]
Setting Parameters:<NRf+>, 0s~100000s, Resolution = 1s, Unit = Second
Setting Example:
ADV:TIM:TOUT 100
Set timeout = 100s
ADV:TIM:TOUT MAX
Set timeout = maximum value.
ADV:TIM:TOUT MIN
Set timeout = minimum value.
Query Syntax:
ADVance:TIMing:TOUT?[<space><MAX | MIN>]
Return Parameters:<NR2>, [Unit = Second]
Query Example:
ADV:TIM:TOUT?
ADV:TIM:TOUT? MAX
ADV:TIM:TOUT? MIN
ADVance:TIMing:TRIGger:MODE
Type:
Channel-Specific
Description:
Set trigger mode in Timing mode.
Setting Syntax:
ADVance:TIMing:TRIGgerMODE<space><CRD | NR1>
Setting Parameters:<CRD | NR1>, FALL(0), RISE(1), HOLDUP(2)
Setting Example:
ADV:TIM:TRIG:MODE RISE
Set trigger mode = Rising edge
ADV:TIM:TRIG:MODE 1
Set trigger mode = Rising edge
Query Syntax:
ADVance:TIMing:TRIGger:MODE?
Return Parameters:<CRD>, FALL, RISE, HOLDUP
[Unit = None]
Query Example:
ADV:TIM:TRIG:MODE?
ADVance:TIMing:TRIGger:VEND
Type:
Channel-Specific
Description:
Set end voltage of trigger when trigger mode set to FALL or RISE in
Timing mode.
Setting Syntax:
ADVance:TIMing:TRIGger:VEND<space><NRf+>[suffix]
Setting Parameters:Refer to respective specification for valid value range.
Setting Example:
ADV:TIM:TRIG:VEND 0.5
Set end voltage = 0.5V
ADV:TIM:TRIG:VEND 500mV
Set end voltage = 0.5V
ADV:TIM:TRIG:VEND MAX
Set end voltage = maximum
value.
ADV:TIM:TRIG:VEND MIN
Set end voltage = minimum value.
Query Syntax:
ADVance:TIMing:TRIG:VEND?[<space><MAX | MIN>]
Return Parameters:<NR2>, [Unit = Volt]
Query Example:
ADV:TIM:TRIG:VEND?
ADV:TIM:TRIG:VEND? MAX
ADV:TIM:TRIG:VEND? MIN
ADVance:TIMing:TRIGger:VSTArt
Type:
Channel-Specific
Description:
Set start voltage of trigger when trigger mode set to FALL or RISE in
Timing mode.
Setting Syntax:
ADVance:TIMing:TRIGger:VSTArt<space><NRf+>[suffix]
Setting Parameters:Refer to respective specification for valid value range.
Setting Example:
ADV:TIM:TRIG:VSTA 0.5
Set start voltage = 0.5V
Summary of Contents for 63600 Series
Page 1: ......
Page 2: ......
Page 8: ...vi...
Page 9: ...vii...
Page 10: ...viii...
Page 16: ......
Page 40: ......
Page 110: ...Programmable DC Electronic Load 63600 Series Operation Programming Manual 4 34...
Page 132: ......
Page 252: ......