Programmable Bidirectional DC Power Supply 62000D Series
Operating and Programming Manual
3-44
4.
Next, tap “START” next to “I source point 2” to perform the second point current
calibration. The DC power supply will output a current of approximately 60.00A. Enter
the accrual current measured by across the current shunt and enter into box for position
[2] and tap “SEND” to confirm.
5.
Repeat above for “I source point 3”. The DC power supply will output a current of
approximately 108.00A. Enter the current measured across the current shunt and enter
into position [3] entry box
and tap “SEND” to confirm.
Figure 3-68
Next perform calibration of negative current points 1, 2 and 3 by following the above
procedure and following display prompts. Calibration points will be -12A, -60A and -108A.
Figure 3-69
Summary of Contents for 62000D Series
Page 1: ......
Page 2: ...Get more information by downloading Chroma ATE Solutions APP ...
Page 8: ...vi ...
Page 9: ...vii ...
Page 10: ...viii ...
Page 14: ......
Page 18: ......
Page 35: ...Overview 1 17 Figure 1 6 Dimension of 62000D 600 1200 1800 Models ...
Page 36: ......
Page 52: ......
Page 63: ...Manual Operation 3 11 Figure 3 13 Figure 3 14 ...
Page 109: ...Manual Operation 3 57 _EXT ON SIGNAL EXT ON DISABLE EXT ON ENABLE Output Output Figure 3 85 ...
Page 110: ......