[DB600] General Instruction Manual
Operation screen (program operation)
- 52 -
□
▲
SEL
↑
↓▼
SEL
O
u
tp
u
t s
w
itc
h
AUTO/
MANUAL output switch
Switch the output between AUTO and MANUAL.
"
□
"
AUTO output
"
"
MANUAL output
For the specification with 2 outputs, the output 1 and output 2 will be changed
simultaneously.
The balance less bump less operation (suppress rapid change in output) is
performed for the output immediately after switching from MANUAL to AUTO output.
When the output is switched from AUTO to MANUAL, the last value of AUTO output
will be used as an initial value of MANUAL output.
Auto tuning will be forced to terminate when MANUAL output is selected during auto
tuning. Note that auto tuning is unavailable during MANUAL output.
The order of priority for output parameters are shown below.
Preset manual output by external signal input
↑ (High)
Priority
↓ (Low)
MANUAL output
RESET output (0%)
PV abnormal output
END output
AUTO output
[Switch to operation initial screen]
Press and hold the [MODE] key to display the screen set on the MODEt operation
initial screen.
[AUTO/MANUAL output switch]
Press and hold the [>] key to switch the output between AUTO and MANUAL.
When switch to the MANUAL output, it will be switched to the PV/OUT1 (operation
screen) automatically.
□
▲
SEL
↑
↓▼
SEL
E
v
e
n
t
Event status
(Alarm event reset)
Checks the event status or reset an alarm event.
"
□
"
No alarm event or status event is activated
"
□
"
to
"
"
Alarm event or status event is activated
(Example)
"
□
"
: Event 1 is activated
"
□
"
: Event 2 is activated
"
□
"
: Event 3 is activated
"
□
"
: Event 4 is activated
"
"
: Event 5 is activated
"
□
"
: Event 6 is activated
"
□
"
: Event 7 is activated
"
□
"
: Event 8 is activated
"
□
"
: Event 9 is activated
"
□
"
: Event 1 and 6 are activated
"
□
"
: Event 2, 4, 7 and 9 are activated
"
"
: Event 1, 3, 5, 7 and 9 are activated
"
"
: All events are activated
"
"
Alarm event reset
When an alarm event is assigned to "Event mode (MODE4)", the alarm event
activation status can be reset. A status event cannot be reset.
Reset an alarm event using the [
], [
] and [ENT] keys.
[Switch to operation initial screen]
Press and hold the [MODE] key to display the screen set on the MODEt operation
initial screen.
[AUTO/MANUAL output switch]
Press and hold the [>] key to switch the output between AUTO and MANUAL.
When switch to the MANUAL output, it will be switched to the PV/OUT1 (operation
screen) automatically.