[DB600] General instruction manual
- 115 -
SV: Setting value
MV: Output value
AL: Event value
db: Event dead-band
Event output range with "Event standby" set
Normal event output range
Event activation range
Setting value upper limit alarm
Upper limit alarm against a setting value (SV).
Activation condition
AL < SV
Keep condition
AL - db < SV
≤ AL
Reset condition
SV
≤ AL - db
Setting value lower limit alarm
Lower limit alarm against a setting value (SV).
Activation condition
AL > SV
Keep condition
AL
≤ SV < AL + db
Reset condition
SV
≥ AL + db
Output value upper limit alarm
Upper limit alarm against an output value.
Activation condition
AL < MV
Keep condition
AL - db < MV
≤ AL
Reset condition
MV
≤ AL - db
Output value lower limit alarm
Lower limit alarm against an output value.
Activation condition
AL > MV
Keep condition
AL
≤ MV < AL + db
Reset condition
MV
≥ AL + db
Event dead-band (db)
Power-ON
Event dead-band (db)
Power-ON
Event dead-band (db)
Power-ON
MV
Event dead-band (db)
Power-ON
MV