[DB600] General Instruction Manual
- 34 -
2-4-2
Procedure of trial operation
After finishing the confirmations before operation, start trial operation refer to the followings and confirm
various contents.
This procedure is the most basic example of trial operation procedure. Add the confirmation contents
according to specifications, system configuration of the final product and control condition of this
instrument.
1.
Turn the power supply ON. Consider the safety, set output to 0% by
manual output operation.
2.
Confirm that device configuring system that also includes this instrument
is normal.
3.
Confirm that the entire signal levels (voltage value, current value, ON/OFF
signal etc.) connected between the devices configuring the system that
also includes this instrument is normal.
4.
When output format is current output format and thyristor regulator is
connected as actuator, confirm the setting contents of thyristor
regulator. When output format is ON-OFF servo output format and the
motor is connected as actuator, perform the actuator adjustment
(feedback zero/span settings). Also in other output format confirm the
actuator and if necessary, perform the adjustment.
5.
Gradually raise the output by manual output etc. and confirm the
operation of actuator is normal according to output value.
6.
Set appropriate SV, switch over from manual output operation to
automatic output operation and set the automatic control status.
7.
Confirm that operation (event, external signal input etc.) with peripheral
device that is connected to this instrument is normal.
8.
Set each type of parameter of this instrument if necessary.
9.
Few hours after starting of the operation, confirm the final product that
includes this instrument and all the devices configuring the system is
normal.