C O N T R O L P A N E L S
Display Software Version
To display the software version, enter the configuration mode (See instructions listed in the
Configuration Mode –
c
n
f
section listed above). When
c
n
f
is displayed, press the
DOWN
button. The software version number will be displayed and should look something like
d.
17
.
Press the DOWN arrow key again to return back to the
c
n
f
display.
Exit the supervisor mode when done.
NOTE:
See Supervisor Mode section on how to exit.
Alarms
Alarm 1 is associated with the heater’s sheath temperature, and is triggered when the
temperature rises above the value set in
al.1
(see chart above).
Alarm 2 is associated with the wash tanks water temperature, and is triggered when the
temperature rises above the value set in
al.2
(see chart above).
When one of these alarms is activated, the circulation pump will turn off and the alarm
indicator light will be illuminated. The controller will enter the
fil
state.
Display Sheath Temperature
During normal operation, pressing the
UP
button will display the heater’s sheath
temperature. The sheath temperature will be displayed for about six seconds and then switch
back to the original display that was shown before the
UP
button was pressed.
Reset Change Water
The Change Water flag is cleared whenever the heaters sheath temperature rises above its set
point. In the case of a heater failure this flag cannot be reset automatically. To manually reset
this flag you will need to hold down the
UP
button and
START/STOP
button
simultaneously for approximately 15 seconds. The controller will then enter the
fil
state.
Display Lamp Test
A lamp test can be started by pressing the
DOWN
and
TEMP
buttons simultaneously.
During the lamp test, the controller functions normally, but all display segments and status
lights flash. Pressing the DOWN and TEMP buttons again will return back to the normal
operation display.
Temperature Sensor Fault
If the water or heater sheath temperature sensors should fail, the controller will indicate the
fault by taking the controller to the
fil
state. The alarm light will be on, the heater will be
disabled, and the circulation pump will be off.
After the sensor(s) have been replaced, normal operation is resumed by exiting the
fil
state.
18
Summary of Contents for Taskmaster PP-3
Page 2: ...Left Blank This Page Intentionally ...
Page 12: ...O P E R A T I O N I N S T R U C T I O N S 11 NOTES ...
Page 48: ...C O N T R O L P A N E L S 47 NOTES ...
Page 52: ...M A I N T E N A N C E 51 NOTES ...
Page 63: ...P A R T S L I S T 62 NOTES ...
Page 64: ...P A R T S L I S T NOTES 63 ...
Page 65: ...P A R T S L I S T NOTES 64 ...
Page 66: ......