Technical data
Rated data
24
CG Drives & Automation
Operation at Heavy duty, overview
4.2.3
Overviewn with heavy duty operation
Input data
Voltage
[V]
Frequency
[Hz]
Heavy Duty
Rated current [A]
Number
of
phases
up to +45 °C
up to +55 °C
CDN40-2P2-65
400/480
50/60
1.8/1.5
1.4/1.1
3
CDN40-3P8-65
400/480
50/60
3.2/2.7
2.4/2.0
3
CDN40-4P8-65
400/480
50/60
3.8/3.1
2.9/2.3
3
CDN40-7P0-65
400/480
50/60
5.6/4.6
4.2/3.5
3
CDN40-8P7-65
400/480
50/60
7.2/5.9
5.4/4.4
3
CDN40-012-65
400/480
50/60
9.3/7.7
7.0/5.8
3
CDN40-016-65
400/480
50/60
12.8/10.6
9.6/8.0
3
Ambient temperature, switching frequency 4 kHz
Output data
Voltage
[V]
Frequency
[Hz]
Heavy Duty
Rated current [A]
Number
of
phases
up to +45 °C
up to +55 °C
CDN40-2P2-65
0 ... 400/480
0 ... 300
1.8/1.5
1.4/1.1
3
CDN40-3P8-65
0 ... 400/480
0 ... 300
3.2/2.7
2.4/2.0
3
CDN40-4P8-65
0 ... 400/480
0 ... 300
3.9/3.2
2.9/2.4
3
CDN40-7P0-65
0 ... 400/480
0 ... 300
5.6/4.7
4.2/3.5
3
CDN40-8P7-65
0 ... 400/480
0 ... 300
7.3/6.0
5.4/4.5
3
CDN40-012-65
0 ... 400/480
0 ... 300
9.5/7.9
7.1/5.9
3
CDN40-016-65
0 ... 400/480
0 ... 300
13.0/10.8
9.8/8.1
3
Ambient temperature, switching frequency 4 kHz
Note!
The maximally possible output voltage is approx. 94 % of the mains
voltage.
Mains
Voltage
U
Lrated
[V]
Voltage range
U
Lrated
[V]
Frequency range
f [Hz]
3/PE AC
400
320
−
0 % ... 440 + 0 %
45
−
0 % ... 65 + 0 %
3/PE AC
480
432
−
0 % ... 528 + 0 %
45
−
0 % ... 65 + 0 %