Technical data
General data and operating conditions
CG Drives & Automation
17
Ambient conditions
Climatic
Storage
IEC/EN
60721−3−1
1K3 (−30 ... +60
°C)
Transport
IEC/EN
60721−3−2
2K3 (−30 ... +75
°C)
Operation
IEC/EN
60721−3−3
3K3 (−30 ... +55
°C)
Operation at 4 kHz: > +45 °C: Reduce the rated
output current by 2.5 %/°C.
Operation at 8/16 kHz: > +40 °C: Reduce the
rated output current by 2.5 %/°C.
Site altitude
< 4000 m amsl
Above 1000 m amsl reduce the rated output
current by 5 %/ 1000 m.
Pollution
IEC/EN
61800−5−1
Degree of pollution 2
Mechanical
Vibration resistance
(9.81 m/s
2
= 1 g)
Motor mounting
Germanischer Lloyd General conditions: Acceleration resistant up to 2 g
IEC/EN
60721−3−3
3M6
Mounting conditions
Mounting place
Motor mounting
Standard
Summary of Contents for CDN40-012-65