Technical data
Rated data
CG Drives & Automation
27
Operation at rated mains voltage 400 V
Fuses and cable
cross−sections
Point−to−point
connection
−
direct wiring of the mains voltage
−
typical fusing
Operation
Type
Installation according to EN 60204−1
1)
Installation
according to
2)
FI
3)
[mA]
[A]
[A]
L1, L2, L3 − laying
system
[A]
L1, L2, L3
[AWG]
B2
[mm
2
]
C
[mm
2
]
F
[mm
2
]
CDN40-2P2-65
C 16
16
2.5
−
−
15
12
30
CDN40-3P8-65
C 16
16
2.5
−
−
15
12
30
CDN40-4P8-65
C 16
16
2.5
−
−
15
12
30
CDN40-7P0-65
C 16
16
2.5
−
−
15
12
30
CDN40-8P7-65
C 16
16
2.5
−
−
15
12
30
CDN40-012-65
C20
20
4.0
−
−
20
12
30
CDN40-016-65
C20
20
4.0
−
−
20
12
30
Multiple connection
−
loop−through
connection of the mains voltage
−
maximum fusing
Operation
Type
Installation according to EN 60204−1
1)
Installation according
to UL
2)
FI
3)
[mA]
[A]
[A]
L1, L2, L3 − laying
system
[A]
L1, L2, L3
[AWG]
B2
[mm
2
]
C
[mm
2
]
F
[mm
2
]
CDN40-2P2-65
C 32
32
6.0
−
−
15
12
30
CDN40-3P8-65
C 32
32
6.0
−
−
15
12
30
CDN40-4P8-65
C 32
32
6.0
−
−
15
12
30
CDN40-7P0-65
C 32
32
6.0
−
−
25
10
30
CDN40-8P7-65
C 32
32
6.0
−
−
25
10
30
CDN40-012-65
C 50
50
16.0
−
−
50
6
30
CDN40-016-65
C 50
50
16.0
−
−
50
6
30
1)
The data are recommendations. Other designs/laying systems can be implemented (e.g. in accordance
with VDE
0298−4).
The cable
cross−sections
apply under the following conditions: Use of
PVC−insulated
copper cables, conductor temperature < 70 °C, ambient temperature < 45°C, no bundling of cables or
cores, three loaded cores.
2)
Only use UL−approved cables, fuses and fuse
holders.
UL fuse: voltage 500 V, tripping characteristic for instance "CC". The cable
cross−sections
apply under the
following conditions: conductor temperature < 75 °C, ambient temperature < 45°C.
3)
Universal−current sensitive earth−leakage circuit breaker, short−time
delayed
Circuit breaker
Fuse of gG/gL utilisation category or semiconductor fuses of gRL utilisation category
Fuse
Observe national and regional regulations