Technical data
Control terminals
38
CG Drives & Automation
General data
4.6.2
General data
General data
Feature
Value/designation
Analog input, voltage
Value range
0 ... 10 V
Resolution
10 bits
Input resistance
>
80 k
Sampling frequency
80 Hz (12 ms)
Accuracy
±0.1 V
Electric strength of external voltage
−
7 ... +30 V
Analog input, current
Value range, parameterisable
0.6 ... +20 mA (< 0.6 mA corresponds to 0)
4 ... +20 mA,
fail−safe
Resolution
10 bits
Input resistance
250
Input current in the case of an open circuit
Display "0" (I < 0.6 mA)
Sampling frequency
80 Hz (12 ms)
Typical accuracy
±0.2 mA
Electric strength of external voltage
−
7 ... +7 V
Digital inputs
Switching level
PLC (IEC
61131−2)
Max. input current
11 mA
Digital outputs
Switching level
PLC (IEC
61131−2)
Max. output current
50 mA
Relay
Contact
NO contact
Connection
AC 250 V, 3 A
DC 24 V, 2 A ... 240 V, 0.16 A
24 V supply
External (24E)
DC input voltage: +19.2 ... +28.8 V
For supporting communication when the mains
voltage is disconnected
Internal (24O)
DC output voltage, max. 100 mA for inputs/outputs
and sensor supply
Interfaces
Extensions
Fieldbus via Communication Unit
Drive interface
Encoder input
Via 2 digital inputs, HTL,
2−track,
10 kHz
Summary of Contents for CDN40-012-65