Commissioning
Before you start
CG Drives & Automation
55
Tip!
In the Default setting, the VFCplus motor control (V/f characteristic control)
with linear characteristic is set in C00006.
VFCplus is especially suitable for the operation of machines with a linear
or
square−law
load torque characteristic (e. g. fan).
The parameters are preset so that, with an inverter that is adapted in terms
of power and a 50 Hz motor, the inverter is ready for operation without
further parameterisation and the motor is working satisfactorily.
Recommendations for the following application cases:
Inverter and motor differing strongly in terms of power:
–
Set code C00022 (I
max
limit in motor mode) to 2 × I
rated
motor.
High starting torque:
–
Set code C00016 (Vmin boost) in
no−load
operation of the motor, so that
the rated motor current is flowing with a rotating field frequency f = 3 Hz
(C00058).
Noise optimisation:
–
Set code C00018 to the value "3" (switching frequency 16 kHz).
High torque at low speeds (without feedback):
–
Select "Vector control" operating mode.