CET Electric Technology
71
26180
RO
Dip N22
UINT32
26182
RO
Dip N32
UINT32
26184
RO
Dip N42
UINT32
26186
RO
Dip N52
UINT32
26188
RO
Dip N62
UINT32
26190
RO
Dip N13
UINT32
26192
RO
Dip N23
UINT32
26194
RO
Dip N33
UINT32
26196
RO
Dip N43
UINT32
26198
RO
Dip N53
UINT32
26200
RO
Dip N63
UINT32
26202
RO
Dip N14
UINT32
26204
RO
Dip N24
UINT32
26206
RO
Dip N34
UINT32
26208
RO
Dip N44
UINT32
26210
RO
Dip N54
UINT32
26212
RO
Dip N64
UINT32
26214
RO
Dip N15
UINT32
26216
RO
Dip N25
UINT32
26218
RO
Dip N35
UINT32
26220
RO
Dip N45
UINT32
26222
RO
Dip N55
UINT32
26224
RO
Dip N65
UINT32
26226
RO
Interruptions N11
UINT32
26228
RO
Interruption N21
UINT32
26230
RO
Interruption N31
UINT32
26232
RO
Ua Transient N1
UINT32
Transient counter occurs on 3-
Phase over 1 week
26234
RO
Ub Transient N1
UINT32
26236
RO
Uc Transient N1
UINT32
* Writing n to the EN50160 Log Pointer register will update the EN50160 Log Buffer with a Log Record at the pointer position.
Table 5-37 EN50160 Log
Notes:
1) Nxx have following definitions:
Swell
(t indicates Duration, while u indicates Residual Voltage)
Counter
10ms <=
t
<= 500ms
500ms < t <= 5000ms
5000ms < t <= 60000ms
t > 60000ms
110% < u < 120%
N11
N21
N31
N41
120% <= u < 140%
N12
N22
N32
N42
140% <= u < 160%
N13
N23
N33
N43
160% <= u < 200%
N14
N24
N34
N44
u >= 200%
N15
N25
N35
N45
Table 5-38 Swell Counter Definition
Dip
(t indicates Duration, while u indicates Residual Voltage)
Counter
10ms < t <=
200ms
200ms < t <=
500ms
500ms < t <=
1000ms
1000ms < t <=
5000ms
5000ms < t <=
60000ms
t >
60000ms
u < 5%
N11
N21
N31
N41
N51
N61
5% <= u < 40%
N12
N22
N32
N42
N52
N62
40% <= u < 70%
N13
N23
N33
N43
N53
N63
70% <= u < 80%
N14
N24
N34
N44
N54
N64
80% <= u < 90%
N15
N25
N35
N45
N55
N65
Table 5-39 Dip Counter Definition
Interruption
(t indicates Duration, while u indicates Residual Voltage)
Counter
t <= 1s
t <= 180000ms
t > 180000ms
N11
N21
N31
Table 5-40 Interruption Counter Definition
5.7 Real-time WFR Register
Register
Property
Description
Format
Note/Range
53000
RO
Start Time
Bitmap
53004
RO
Reserved
Unit16
53005
RO
Reserved
Unit16
53006
RO
Frequency
Float
53008
RO
Ia 1
st
Sample
Float
Summary of Contents for PMC-690
Page 1: ...PMC 690 Hand Held Power Quality Analyzer User Manual Version V1 0A Aug 27 2018...
Page 21: ...CET Electric Technology 21 Energy Demand Harmonics Spectrum Table Power...
Page 23: ...CET Electric Technology 23 Max Min Setup Basic Device Storage...
Page 24: ...CET Electric Technology 24 Advanced...
Page 26: ...CET Electric Technology 26 Monitoring History Table 3 2 Description of each Hierarchy...