CET Electric Technology
40
Flagging
Status
This
register indicates if a particular type of data has been
flagged
with a bit value of
1 meaning
flagged
and 0 meaning
not flagged
. The following table illustrates the
details of the
Flagging
Status
register for real-time data.
Bit
Description
Bit
Description
B0
Basic Measurement
Dip
B8
Pst.
Dip
B1
Swell
B9
Swell
B2
Interruption
B10
Interruption
B3
Over Current Limit
B11
Reserved
B4
Freq.
Dip
B12
Plt.
Dip
B5
Swell
B13
Swell
B6
Interruption
B14
Interruption
B7
Reserved
B15
Reserved
Table 4-19 Flagging Status Register (0080)
Statistical Log
For any Statistical Log (such as SDR Log, Max. Log, Min. Log and/or EN50160 Log), its
log entry will be discarded and will not be included in the statistical evaluation if any
data within the log entry has been
Flagged
while
the bit representing the particular
Log type in the
Flagging Setup
register is enabled (set to 1).
Real-time Data
Real-time data via Modbus communications will only refresh after the
Flagging Status
register
has been read if Bit 15 of the
Flagging Setup
register is enabled (set to 1) and
if
Flagging
is active. Conversely, real-time data via Modbus communications will
automatically refresh if Bit 15 of the
Flagging Setup
register is disabled
(set to 0) so
there is no need to read the
Flagging Status
register
before reading the real-time data.
Real-time data includes Frequency, Voltage, Current, Unbalance, Harmonics and
Interharmonics measurements.
4.3.14 EN50160 Compliance Report
The EN50160 Standard defines the
Voltage Characteristics of Electricity Supplied by Public Distribution
Systems
. It provides the limits within which any customer can expect voltage characteristics to remain.
For a complete definition of the non-conformity level for each of the following EN50160 parameters,
please refer to the EN50160 Standard document.
The PMC-690 can measure, summarize data and statistics relevant data in accordance with the EN50160
standard. In addition, the device is capable of creating a report per week for the following PQ
parameters and the report can be stored for one year.
Power Frequency, including Maximum and Minimum
Supply Voltage Variations, including Maximum and Minimum
Flicker, including Max./Min. and CP95
Voltage Unbalance, including Max./Min. and CP95
Harmonic Voltage, including Max./Min., Avg. and CP95
Mains Signal Voltage, including Max./Min. and CP95
Rapid Voltage Changes
Swells and Dips, statistic parameters classified according to characteristic voltage and duration
Interruptions, statistics parameters classified according to duration
Transients
The programming of EN50160 Log only supports communications, please refer to
Section 5.8.12
to set
parameters for each item. EN50160 Report can be accessed through the Front Panel or via
Summary of Contents for PMC-690
Page 1: ...PMC 690 Hand Held Power Quality Analyzer User Manual Version V1 0A Aug 27 2018...
Page 21: ...CET Electric Technology 21 Energy Demand Harmonics Spectrum Table Power...
Page 23: ...CET Electric Technology 23 Max Min Setup Basic Device Storage...
Page 24: ...CET Electric Technology 24 Advanced...
Page 26: ...CET Electric Technology 26 Monitoring History Table 3 2 Description of each Hierarchy...