CET Electric Technology
53
one for every
Device / SOE Log
generated and will roll over to 0 if its current value is 0xFFFFFFFF. Since the
Device /SOE Log
Pointer
is a 32-bit value and the
Device / SOE Log
capacity is relatively small with only 1024 entries
in the PMC-690, an
assumption has been made that the
Device / SOE Log pointer
will never roll over. If a
Clear Device / SOE Log
is performed
from the front panel or via communications, the
Device / SOE Log Pointer
will be reset to zero. Therefore, any 3rd party
software should assume that a
Clear Device / SOE Log
action has been performed if it sees the
Device / SOE Log Pointer
rolling over to zero or to a value that is smaller than its own pointer. In this case, the new
Device / SOE Log Pointer
also
indicates the number of logs in the
Device / SOE Log
if it is less than 1024. Otherwise, there will always be
1024 entries in
the
Device / SOE Log
.
5)
The PMC-690 has 5 Statistical Data Recorder Logs (
SDR Log #1 to 5
). Each
SDR
Log
has a pointer that indicates its present
logging position. The range of the
SDR Log Pointer
is between 0 and 0xFFFFFFFF. The
SDR Log Pointer
is incremented by
one for every
SDR Log
generated and will roll over to 0 if its current value is 0xFFFFFFFF. A value of zero indicates that the
device does not contain any
SDR Log
. If a
Clear All SDR
Log
is performed via communications, all
SDR Log Pointers
will be
reset to zero.
To determine the latest
SDR Log
#X
location (X=1 to 5):
SDR Log
#X
latest location = Modulo [
DR Pointer #X / DR #X Depth
]
6)
WFR
Log
has a pointer that indicates its present logging position. The range of the
WFR Log Pointer
is between 0 and
0xFFFFFFFF. The
WFR Log Pointer
is incremented by one for every
WFR Log
generated and will roll over to 0 if its current
value is 0xFFFFFFFF. A value of zero indicates that the device does not contain any
WFR Log
. The depth of
WFR Log
is 500
entries. Since the
WFR Log Pointers
are 32-bit values, an assumption has been made that these pointers will never roll over.
If a
Clear WFR
log is performed via communications, the
WFR Log Pointers
will be reset to zero.
To determine the latest
WFR Log
location:
WFR Log
latest location = Modulo [
WFR Log Pointer
/
WFR Log Depth
]
5.2 Energy Measurements
Register
Property
Description
Format
Unit
0500
RW
kWh Imp.
INT64
wh
0504
RW
kWh Exp.
INT64
wh
0508
RW
kvarh Imp.
INT64
varh
0512
RW
kvarh Exp.
INT64
varh
0516
RW
kVAh Total
INT64
VAh
0520
RO
kWh Net
INT64
wh
0524
RO
kWh Total
INT64
wh
0528
RO
kvarh Net
INT64
varh
0532
RO
kvarh Total
INT64
varh
0536
RO
Reserved
INT64
Table 5-5 Energy Measurements
5.3 PQ Measurements
Register
Property
Description
Format
Unit
0700
RO
Ua Deviation
1
Float
0702
RO
Ub Deviation
1
Float
0704
RO
Uc Deviation
1
Float
0706
RO
Uab Deviation
Float
0708
RO
Ubc Deviation
Float
0710
RO
Uca Deviation
Float
0712
RO
Over Ua Deviation
1
Float
0714
RO
Over Ub Deviation
1
Float
0716
RO
Over Uc Deviation
1
Float
0718
RO
Over Uab Deviation
Float
0720
RO
Over Ubc Deviation
Float
0722
RO
Over Uca Deviation
Float
0724
RO
Under Ua Deviation
1
Float
0726
RO
Under Ub Deviation
1
Float
0728
RO
Under Uc Deviation
1
Float
0730
RO
Under Uab Deviation
Float
0732
RO
Under Ubc Deviation
Float
0734
RO
Under Uca Deviation
Float
0736
RO
Freq. Deviation
Float
Hz
0738
RO
Ua (WYE) / Uab (Delta) Fluctuation
Float
0740
RO
Ub (WYE) / Ubc (Delta) Fluctuation
Float
0742
RO
Uc (WYE) / Uca (Delta) Fluctuation
Float
0744
RO
Ua (WYE) / Uab (Delta) Fluctuation Freq.
Float
0746
RO
Ub (WYE) / Ubc (Delta) Fluctuation Freq.
Float
0748
RO
Uc (WYE) / Uca (Delta) Fluctuation Freq.
Float
Summary of Contents for PMC-690
Page 1: ...PMC 690 Hand Held Power Quality Analyzer User Manual Version V1 0A Aug 27 2018...
Page 21: ...CET Electric Technology 21 Energy Demand Harmonics Spectrum Table Power...
Page 23: ...CET Electric Technology 23 Max Min Setup Basic Device Storage...
Page 24: ...CET Electric Technology 24 Advanced...
Page 26: ...CET Electric Technology 26 Monitoring History Table 3 2 Description of each Hierarchy...