Figure 4-2 Under Setpoint
The Setpoints can be programmed over communications and have the following setup parameters:
Setup Parameter
Definition
Options
Setpoint Type
Specify the monitoring condition -- Over Setpoint, Under Setpoint.
0=Over Setpoint*
1=Under Setpoint
Setpoint Parameter
Specify the parameter to be monitored.
See Table 4-5
Setpoint Active Limit
Specify the value that the setpoint parameter must exceed for Over Setpoint
or go below for Under Setpoint for the setpoint to become active.
0*
Setpoint
Inactive
Limit
Specify the value that the setpoint parameter must go below for Over Setpoint
or exceed for Under Setpoint for the setpoint to becomes inactive.
0*
Setpoint
Active
Delay
Specify the minimum duration that the setpoint condition must be met before
the setpoint becomes active. An event will be generated and stored in the SOE
Log. The range of the
Setpoint Active Delay
is between 0 and 9999 seconds
for Standard Setpoints and between 0 and 9999 cycles for High Setpoints.
0* to 9999s
Setpoint
Inactive
Delay
Specify the minimum duration that the setpoint return condition must be met
before the setpoint becomes inactive. An event will be generated and stored
in the SOE Log. The range of the
Setpoint Inactive Delay
is between 0 and
9999 seconds for Standard Setpoints and between 0 and 9999 cycles
for High
Setpoints.
0* to 9999
Setpoint Trigger
Specify what action a setpoint can take when it becomes active. Please refer
to Table 4-6 below for a list of Setpoint Triggers.
0*
*Default
Table 4-4 Description for Setpoint Parameters
Key
Parameter
Key
Parameter
Key
Parameter
1
ULN*
25
U TEHD
49
kW Exp. Total Demand
2
ULL*
26
I THD
50
kvar Exp. Total Demand
3
U4*
27
I TOHD
51
kVA Total Demand
4
Ia/Ib/Ic*
28
I TEHD
52
P.F. Total Demand
5
I4*
29
U TIHD
53
kW Imp. Total Pred. DMD
6
Reserved*
30
U TOIHD
54
kvar Exp. Total Pred. DMD
7
kW Total*
31
U TEIHD
55
kW Exp. Total Pred. DMD
8
kvar Total*
32
I TIHD
56
kvar Exp. Total Pred. DMD
9
kVA Total*
33
I TOIHD
57
kVA Pred. Total DMD
10
P.F. Total*
34
I TEIHD
58
P.F. Pred. Total DMD
11
U0 Unbalance
35
U TH RMS
59
Pst
12
U2 Unbalance
36
U TOH RMS
60
Plt
13
I0 Unbalance
37
U TEH RMS
61
Voltage Fluct.
14
I2 Unbalance
38
I TH RMS
0x0002xxxx
U HD02
15
U Fundamental
39
I TOH RMS
…
U HD03~HD62
16
I Fundamental
40
I TEH RMS
0x003fxxxx
U HD63
17
U Deviation
41
U TIH RMS
0x0081xxxx
U IHD01
18
U Over Deviation
42
U TOIH RMS
…
U IHD02~IHD62
19
U Under Deviation
43
U TEIH RMS
0x00bfxxxx
U IHD063
20
Frequency
44
I TIH RMS
0x02xxxxxx
I HD02
Summary of Contents for PMC-690
Page 1: ...PMC 690 Hand Held Power Quality Analyzer User Manual Version V1 0A Aug 27 2018...
Page 21: ...CET Electric Technology 21 Energy Demand Harmonics Spectrum Table Power...
Page 23: ...CET Electric Technology 23 Max Min Setup Basic Device Storage...
Page 24: ...CET Electric Technology 24 Advanced...
Page 26: ...CET Electric Technology 26 Monitoring History Table 3 2 Description of each Hierarchy...