CET Electric Technology
43
Number of Parameters
0 to 64 (user defined)
64
Parameters 1 to 64
See
Section 5.8.10
Table 4-22 Setup Parameters for SDR
The
SDR Log
is only operational when the values of
Recording Interval
and
Number of Parameters
are
all non-zero.
4.4.3 Max./Min. Log
The PMC-690 provides 4 Max./Min. Logs and capable of recording 20 parameters each since Last Reset
(This Month) or before Last Reset (Last Month). Each record includes relevant parameter values and
timestamp. The recorded data is stored in non-volatile memory and will not suffer any loss in the event
of a power failure. All Max./Min. Log can be accessed over communication.
The PMC-690’s Max./Min. Log can record the following parameters:
Max./Min. Parameters
Ua
Ub
Uc
Uab
Ubc
Uca
Ia
Ib
Ic
kW Total
kvar Total
kVA Total
P.F. Total
Ua Pst
Ub Pst
Uc Pst
Ua Plt
Ub Plt
Uc Plt
Ua Over
Deviation
Ub Over
Deviation
Uc Over
Deviation
Uab Over/Under
Deviation
Ubc Over/Under
Deviation
Uca Over/Under
Deviation
Freq. Deviation
U0 Unbal.
U2 Unbal.
I0 Unbal.
I2 Unbal.
U4 RMS
I4 RMS
U1
U0
I1
I0
Ua THD
Ub THD
Uc THD
Ia THD
Ib THD
Ic THD
kW Total TH
kvar Total TH
kVA Total TH
P.F. Total TH
kW Total H01
kvar Total H01
kVA Total H01
P.F. Total H01
Frequency
Ia/Ib/Ic/I4
K-Factor
U2
I2
Table 4-23 Max./Min. Measurements
The programming of the Max./Min. Log is only supported over communications. Each Max./Min. Log
provides the following setup parameters:
Parameters
Value
Self-Read time
A zero value means that the Self-Read will take place at 00:00 of the first day of each month.
(Default)
A non-zero value means that the Self-Read will take place at a specific time and day based
on the formula: Self-Read Time = Day * 100 + Hour where 0 ≤ Hour ≤ 23 and 1 ≤ Day ≤ 28.
For example, the value 1512 means that the Self-Read will take place at 12:00pm on the 15
th
day of each month.
A 0xFFFF value will disable the Self-Read operation and replace it with manual operation. A
manual reset will cause the Max./Min. Log of
This Month
to be transferred to the Max/Min.
Log of
Last Month
and then reset. The terms
This Month
and
Last Month
will become
Since
Last Reset
and
Before Last Reset
.
Number of Parameters
0 to 20
Parameter 1 to 20
All real-time data can be configured to parameters, please see
Section 5.8.11
Table 4-24 Setup Parameters for Max./Min. Log
4.4.4 Pst Log
The PMC-690’s Pst Log
can store up to 52560 events per 10 minutes about voltage Pst in its non-volatile
memory. Each event record includes the event classification, its relevant parameter values and a
timestamp in 1ms resolution.
All events can be retrieved via communications for display. If there are more than 52560 events, the
newest event will replace the oldest event on a first-in-first-out basis. The Pst Log can be reset from the
front panel or via communications.
Summary of Contents for PMC-690
Page 1: ...PMC 690 Hand Held Power Quality Analyzer User Manual Version V1 0A Aug 27 2018...
Page 21: ...CET Electric Technology 21 Energy Demand Harmonics Spectrum Table Power...
Page 23: ...CET Electric Technology 23 Max Min Setup Basic Device Storage...
Page 24: ...CET Electric Technology 24 Advanced...
Page 26: ...CET Electric Technology 26 Monitoring History Table 3 2 Description of each Hierarchy...