13-8
13.7 Parameter code list <Common area>
<Common area>: Area accessible regardless of inverter models (Note 3)
Address Parameter
Scale Unit R/W
Data value
3: H series
4: S series
7: G series
0x0000 Inverter model
R
8: C series
9: P series
A: GS series
FFFF: 0.4kW 0000: 0.75kW 0002: 1.5kW
0x0001 Inverter capacity
R
0003: 2.2kW 0004: 3.7kW 0005: 4.0kW
0006: 5.5kW 0007: 7.5kW
0x0002 Inverter Input Voltage
R
0: 220V class
1: 440V class
(Ex) 0x0100: Version 1.0
0x0003 S/W Version
R
0x0101: Version 1.1
0x0004 Parameter Lock
R/W
0: Lock (default)
1: Unlock
0x0005 Frequency Reference 0.01 Hz R/W Starting freq. ~ Max. freq.
BIT 0: Stop (S)
BIT 1: Forward run (F)
R/W
BIT 2: Reverse run (R)
BIT 3: Fault reset (0->1)
W
BIT 4: Emergency stop
-
BIT 5: Not used
BIT 6~7: Output freq. arrival
0(Terminal), 1 (keypad)
2(Reserved), 3 (communication)
BIT 8~12: Freq. command
0 ~ 8: Multi-step speed freq. (0, 2~8)
9 ~ 11: UpDown (Up, Down, UDZero)
12 ~ 16: Analog (V0, V1, I, V0I, V1I)
17: Jog, 18: PID, 19: Communication
R
20 ~ 31: Reserved
0x0006
Run Command
(Note 1)
-
BIT 15: Not used
0x0007 Acceleration Time
0.1
sec R/W
0x0008 Deceleration Time
0.1
sec R/W
0x0009 Output Current
0.1
A
R
0x000A Output Frequency
0.01 Hz R
0x000B Output Voltage
0.1
V
R
See Function List.
Summary of Contents for Titan CI-001-GS2
Page 1: ...D GS S Compact Space Ve VFD Frequency and 5 5 5 5 8...
Page 13: ...1 4 Notes...
Page 16: ...2 3 2 2 Dimensions CI 002 GS2 4 CI 001 GS2 4...
Page 17: ...2 4 CI 003 GS2 4 CI 005 GS2 4 CI 007 GS2 4 CI 010 GS2 4 H W D W1 A A H1 W1 B B...
Page 19: ......
Page 25: ...3 6 5 5 7 5 kW 5 5 mm2 M4 3 5 mm2 M4...
Page 45: ...6 4 Notes...
Page 68: ...CHAPTER 8 CONTROL BLOCK DIAGRAM m G k G h Vk Vm w t t...
Page 71: ...8 4 Notes...
Page 119: ...10 26 Notes...
Page 141: ...12 10 Ex 2 100 2 _ _ 1 _ _ _ 76 u steady T acc T steady T dec T dec T H m U X Y...
Page 159: ...13 18 Notes...
Page 169: ...15 4...
Page 170: ...15 5 Notes...
Page 171: ......