11-1
CHAPTER 11 -
MONITORING
11.1 Operating status monitoring
z
Output current
Group
Display
Parameter Name
Setting
Range
Default Unit
Drive group
CUr
[Output current]
-
Inverter output current can be monitored in Cur.
z
Motor RPM
Group
Display
Parameter Name
Setting
Range
Default Unit
Drive group
rPM
[Motor RPM]
-
H31
[Number of motor poles]
-
2 ~ 12
4
H40
[Control mode select]
-
0 ~
3
0
Function
group 2
H74
[Gain for Motor rpm
display]
-
1 ~ 1000 100
%
Motor rpm can be monitored in rPM.
When H40 is set to 0 {V/F control} or 1 {PID control}, the Inverter output frequency
(f) is displayed in RPM using the formula below. Motor slip is not considered.
H31: Enter the number of rated motor poles on the nameplate.
H74: This parameter is used to change the motor speed display to rotating speed
(r/min) or mechanical speed (m/min).
z
Inverter DC Link Voltage
Group
Display
Parameter Name
Setting
Range
Default Unit
Drive group
dCL
[Inverter DC Link
Voltage]
-
Inverter DC link voltage can be monitored in dCL.
2
times the value of input voltage is displayed while motor is at a stop.
100
74
31
120
H
H
f
RPM
u
¸
¹
·
¨
©
§
u
Summary of Contents for Titan CI-001-GS2
Page 1: ...D GS S Compact Space Ve VFD Frequency and 5 5 5 5 8...
Page 13: ...1 4 Notes...
Page 16: ...2 3 2 2 Dimensions CI 002 GS2 4 CI 001 GS2 4...
Page 17: ...2 4 CI 003 GS2 4 CI 005 GS2 4 CI 007 GS2 4 CI 010 GS2 4 H W D W1 A A H1 W1 B B...
Page 19: ......
Page 25: ...3 6 5 5 7 5 kW 5 5 mm2 M4 3 5 mm2 M4...
Page 45: ...6 4 Notes...
Page 68: ...CHAPTER 8 CONTROL BLOCK DIAGRAM m G k G h Vk Vm w t t...
Page 71: ...8 4 Notes...
Page 119: ...10 26 Notes...
Page 141: ...12 10 Ex 2 100 2 _ _ 1 _ _ _ 76 u steady T acc T steady T dec T dec T H m U X Y...
Page 159: ...13 18 Notes...
Page 169: ...15 4...
Page 170: ...15 5 Notes...
Page 171: ......