12-9
12.8 DB Resistor Enable Duty setting
Group
Code
Parameter
Set
Range
Initial
Unit
H75
[Enable duty limit]
1
0 ~ 1
1
Function
group 2
H76
[Enable duty]
-
0 ~ 30
10
%
Set H75 to 1.
Set %ED (Enable Duty) in H76.
H75: DB resistor ED limit setting
No limit
0
ჹ
Caution:
Take caution when DB resistor is used over its Watt rating. Fire may
result from resistor overheat. When resistor having heat detection sensor
is used, sensor output can be used as external trip signal in multi-
function input.
1
ED is limited as the setting in H 76.
H76: set the resistor operating rate(%ED) in one sequence of operation. Continuous
usage reate is Max 15 sec and usage signal is not issued over 15 sec.
Ex 1)
[%]
100
_
_
_
_
_
76
u
stop
T
dec
T
steady
T
acc
T
dec
T
H
Where,
T_acc: Acceleration time to reach a setting freq.
T_steady: Time for constant speed operation at setting freq.
T_dec: Time to decelerate to lower freq. than that in constant speed
or time to stop from freq. in constant speed.
T_stop: waiting time at a stop before operation is resumed.
mU
{
{ {
{
Summary of Contents for Titan CI-001-GS2
Page 1: ...D GS S Compact Space Ve VFD Frequency and 5 5 5 5 8...
Page 13: ...1 4 Notes...
Page 16: ...2 3 2 2 Dimensions CI 002 GS2 4 CI 001 GS2 4...
Page 17: ...2 4 CI 003 GS2 4 CI 005 GS2 4 CI 007 GS2 4 CI 010 GS2 4 H W D W1 A A H1 W1 B B...
Page 19: ......
Page 25: ...3 6 5 5 7 5 kW 5 5 mm2 M4 3 5 mm2 M4...
Page 45: ...6 4 Notes...
Page 68: ...CHAPTER 8 CONTROL BLOCK DIAGRAM m G k G h Vk Vm w t t...
Page 71: ...8 4 Notes...
Page 119: ...10 26 Notes...
Page 141: ...12 10 Ex 2 100 2 _ _ 1 _ _ _ 76 u steady T acc T steady T dec T dec T H m U X Y...
Page 159: ...13 18 Notes...
Page 169: ...15 4...
Page 170: ...15 5 Notes...
Page 171: ......