Temperature
2.x. DHW
2.x.1 DHW temp.
The default temperature of the
DHW tank.
DHW temp.
50
Factory:
min./max.
40 / 80 °C
2.x.2 Differential of DHW
The default differential for starting the DHW
tank to warm up (Tdhw-dTdhw).
2.x. Buffer tank
2.x.1. Buffer tank temp.
Default buffer tank temperature (measured on the upper sensor).
2.x.2. Min buf. tank temp.
Default minimum buffer tank temperature (measured on the upper sensor) - when reached, the
heating pumps behind the storage tank are switched off.
2.x.3. Diff. buf. tank temp.
Default differential to start warming up the buffer
tank (measured on the upper sensor)
(Tbuff-dTbuff).
2.x.4. Diff. stop buff. tank
Default differential to turn OFF warming up the
AKU. tank (measured on the lower sensor)
(Tbuff-dTbuff off).
Buffer tank temp.
80
Factory:
min./max.
40 / 85 °C
Min buf. tank temp.
20
5 / 66 °C
Diff. buf. tank temp
10
5 / 30 °C
Dif. stop buff. tank
5
3 / 30 °C
2.x.1. Crossover temp.
Hydraulic crossover temperature setpoint.
Crossover temp.
80
Factory:
min./max.
75 / 85 °C
Differential of DHW
5
Factory:
min./max.
4 / 40 °C
2.1.4. Heating curve
Adjustment of the coefficient (slope) of the heating curve of the selected heating circuit
(dependence of the flow temperature on the outside temperature). Depending on the type of
heating installed and the thermal insulation of the building, the slope of the heating curve must be
adjusted - it is usually recommended for radiator heating curves from 1.0 to 4.0 and for underfloor
heating from 0.1 to 0.9.
2.1.5. Correction coeff.
Determination of the coefficient of influence of the room corrector on the flow temperature. The
higher this coefficient, the room corrector will have a greater influence on the calculated required
flow temperature of the selected heating circuit.
2.1.2. Day room temp.
Selects the default daily room temperature.
2.1.3. Night room temp.
Selects the default night room temperature.
Day room temp.
20
Factory:
min./max.
5 / 30 °C
Night room temp.
20
5 / 30 °C
Heating curve
1.0
0,1 / 4.0
Correction coeff
1.0
0.1 / 5.0
2.x.x. Wood (only with BioTec-L and BioTec Plus)
2..x.1. Boiler temp.
Default boiler temperature
2..x.2. Diff. Boiler
Default differential temperature
Boiler temp.
85
Factory
min./max.
75 / 90 °C
Diff. Boiler
5
5 / 7 °C
ENG
Technical instructions
C
SK-Touch
34