17.2
Supply the Electronic Board
The REVO M thyristor unit, to work, requires a voltage supply for the electronic boards. The Max
consumption is 10VA.
The voltage supply for the electronic boards is configured in line with customer requirements that are
defined in the Order Code. The Order Code is written on the identification label.
Warning:
Before connecting or disconnecting the unit check that power and control cables
are isolated from voltage sources.
Terminal M4
M4
Description
1
Voltage Supply for Electronic Boards (Auxiliary Voltage)
2
Not Used
3
Voltage Supply for Electronic Boards (Auxiliary Voltage)
To change auxiliary supply voltage sold the correct link-jumper on CD6000M board
The type of mounted transformer depends of the chosen Voltage in the order code.
Transformer Type
Link-Jumper JP1+JP2
Link-Jumper JP3
TR-605 120V
90:130V
-
TR-605 230V
170:265V
300:530V
TR-605 300V
230:345V
510:690V
If the Auxiliary Voltage (written on the identification label) is different from Supply Voltage (to the load),
use an external transformer with primary equal to load voltage and secondary equal to the Auxiliary
Voltage
M4
Summary of Contents for Revo M 1PH
Page 2: ...CD Automation srl REVO M User s Manual REVO_M08 2 ...
Page 19: ...CD Automation srl REVO M User s Manual REVO_M08 19 11 2 Schematic ...
Page 24: ...CD Automation srl REVO M User s Manual REVO_M08 24 12 1 Scroll the parameters ...
Page 32: ...CD Automation srl REVO M User s Manual REVO_M08 32 17 Electronic boards 17 1 How to access ...
Page 48: ...CD Automation srl REVO M User s Manual REVO_M08 48 ...