CD Automation srl
REVO M
User’s Manual
REVO_M08
17
11
Wiring instructions
The Thyristor unit could be susceptible to interferences lost by near equipments or by the power supply,
for this reason in accord to the fundamental practices rules is opportune take some precautions:
•
The coil contactor, the relays and other inductive loads must be equipped with opportune RC filter.
•
Use shielded bipolar cables for all the input and output signals.
•
The signal cables must not be near and parallel to the power cables.
•
Local regulations regarding electrical installation should be rigidly observed.
Use copper cables and wires rated for use at 75°C only.
Power cable torque (suggested)
Type
Connector
Type
Torque
Lb-in (N-m)
Wire Range
mm²(AWG )
MAX Current
Terminals
Wire Terminals
UL Listed (ZMVV)
030
035
040
045
Screw M5
26.6 (3.0)
1.5-10 (16-8)
45A
Rigid / Flexible
Spade Terminal
Cable dimensions of the Command Terminals
0.5
mm² (AWG 18)
Cable dimensions of the Earth (suggested)
6
mm² (AWG 10)
Warning:
Before connecting or disconnecting the unit check that power and control cables
are isolated from voltage sources.
Terminal
Description
L1
Line Input Phase 1
T1
Load Output Phase 1
L2
Line Input Phase 2 (only for 3pH)
T2
Load Output Phase 2 (only for 3pH)
L3
Line Input Phase 3 (only for 2Ph and 3Ph)
T3
Load Output Phase 3 (only for 2Ph and 3Ph)
Summary of Contents for Revo M 1PH
Page 2: ...CD Automation srl REVO M User s Manual REVO_M08 2 ...
Page 19: ...CD Automation srl REVO M User s Manual REVO_M08 19 11 2 Schematic ...
Page 24: ...CD Automation srl REVO M User s Manual REVO_M08 24 12 1 Scroll the parameters ...
Page 32: ...CD Automation srl REVO M User s Manual REVO_M08 32 17 Electronic boards 17 1 How to access ...
Page 48: ...CD Automation srl REVO M User s Manual REVO_M08 48 ...