CD Automation srl
REVO M
User’s Manual
REVO_M08
25
13
Input output signal
13.1
Digital Input
The REVO M thyristor unit has 2 digital inputs opto-isolated to 24Vdc 5 mA.
You can activate the inputs with the internal supply or with an external source for example the PLC.
13.1.1
Start/Stop (Terminal 3 of M2)
This is the start command (Enable) of the REVO M.
If you Remove the Start command the REVO M thyristor unit will be stopped and the output will return
at zero.
13.1.2
Configurable Input (Terminal 4 of M2)
This digital input is configured by the parameter
and could perform different functions:
•
Enable:
This function forces the output at zero.
•
Feed-Back Selection:
With this function, when you active the input, the feed-back setted in the parameter
change in
Voltage Feed-Back (V).
•
Analog/Digital Setpoint(Local/Remote:
With this function, when you active the input, the setpoint reference change from Analog input to
Digital value, setted in the parameter
.
•
Change Firing type:
With this function, when you active the input, the Firing type setted in the parameter
change in
Phase Angle PA (available only on 1PH).
13.2
Digital Output terminal
(terminal
14-15-16 of M1)
The REVO M thyristor unit has 1 relay output on terminal 14-15-16 of terminal block M1
(Max 500mA, 125Vac). The functionality of this output cane be setted with the parameter
This digital output can be configured in order to activate itself after that one of these alarms occours:
•
HB and SC alarm are active.
•
Only HB alarm is active.
•
Only SC alarm is active.
13.3
Analog Input
Primary Input (Terminals 5 and 6 of M2)
The REVO M thyristor unit has 1 analog inputs (0÷10V, 0÷20mA, 4÷20mA ecc):
The primary input for the analog setpoint.
The primary input is already configured in line with customer requirements that are defined in the Order
Code. The Order Code is written on the identification label.
However, if you wish to change the primary input (ex. from 0÷10V to 0÷20mA, 4÷20mA).
Summary of Contents for Revo M 1PH
Page 2: ...CD Automation srl REVO M User s Manual REVO_M08 2 ...
Page 19: ...CD Automation srl REVO M User s Manual REVO_M08 19 11 2 Schematic ...
Page 24: ...CD Automation srl REVO M User s Manual REVO_M08 24 12 1 Scroll the parameters ...
Page 32: ...CD Automation srl REVO M User s Manual REVO_M08 32 17 Electronic boards 17 1 How to access ...
Page 48: ...CD Automation srl REVO M User s Manual REVO_M08 48 ...