CD Automation srl
REVO M
User’s Manual
REVO_M08
34
17.3
Analog Inputs
The REVO M thyristor unit has 2 configurable analog inputs (0÷10V, 4÷20mA, ecc):
The primary input for the analog setpoint, the secondary input for the Current Profiler or Ext. Feed-Back.
17.3.1
Primary Input (Terminals 5 and 6 of M2)
The primary input is already configured in line with customer requirements that are defined in the Order
Code. The Order Code is written on the identification label.
However, if you wish to change the primary input (ex. from 0÷10V to 4÷20mA) proceed as follows:
A
B
C
A
B
C
A
B
C
Type
Input features
Jumper
0
÷
10V (default)
Impedance
15K
Ω
Open
POT
Impedance
10K
Ω
min
Open
4
÷
20mA
Impedance
100
Ω
Close
Primary Input calibration procedure
When you change the hardware setting is necessary make the Input calibration procedure.
To make the Input calibration procedure follow these steps:
•
Give the power supply.
•
With Control Panel go in the Hardware menu (
= 5)
•
Set the input signal to the min value (ex. 0V for 0÷10V or 4mA for 4÷20mA)
•
Set the parameter
= 1
•
Press ENTER key
•
Set the input signal to the max value (ex.10V for 0÷10V or 20mA for 4÷20mA)
•
Set the parameter
= 1
•
Press ENTER key
The Input calibration procedure is done.
Summary of Contents for Revo M 1PH
Page 2: ...CD Automation srl REVO M User s Manual REVO_M08 2 ...
Page 19: ...CD Automation srl REVO M User s Manual REVO_M08 19 11 2 Schematic ...
Page 24: ...CD Automation srl REVO M User s Manual REVO_M08 24 12 1 Scroll the parameters ...
Page 32: ...CD Automation srl REVO M User s Manual REVO_M08 32 17 Electronic boards 17 1 How to access ...
Page 48: ...CD Automation srl REVO M User s Manual REVO_M08 48 ...