6
Quick Start
Attention:
this procedure must be carried out by skilled people only.
If your REVO M code is in line with what you really need, then the main configuration is already done by
CD Automation and you just need to do the following steps:
1.
Verify REVO M’s current sizing. Be sure that:
•
the load current is equal or less than the nominal one of REVO M
•
the main voltage is equal or less than the nominal voltage of REVO M
2.
Verify the Installation
3.
Verify the Wiring:
•
all auxiliary connections must be done in line with wirings on this manual
•
verify that there isn’t a short circuit on the load
4.
Supply the auxiliary voltage of the unit
Set the parameters U_OP (Operative Voltage) and A_Lo (Nominal Current of the load) using the
frontal keypad or CDA Thyristor configurator software.
Operative Voltage
V
R/W
Function:
It’s necessary to specify the operative voltage
Min/Max:
24 ÷ 1000V
Default:
230
Note:
With voltage up to 330V and over 600V, REVO M needs hardware
modifications: specify this in phase of ordination.
Load nominal current
A
R/W
Function:
It’s necessary to specify the load current value at nominal voltage.
This current and voltage value are necessary to be able to read the
power in engineering units
Min/Max:
1 ÷ 100.0 Ampere (for size up to 100A)
Default:
Nominal REVO M current value if load current has not been specified.
If your REVO M code is NOT in line with what you really need, use the enclosed configurator
software tool to set-up the unit. Install the software on your PC, select REVO M and click on
test unit changing what you need.
Summary of Contents for Revo M 1PH
Page 2: ...CD Automation srl REVO M User s Manual REVO_M08 2 ...
Page 19: ...CD Automation srl REVO M User s Manual REVO_M08 19 11 2 Schematic ...
Page 24: ...CD Automation srl REVO M User s Manual REVO_M08 24 12 1 Scroll the parameters ...
Page 32: ...CD Automation srl REVO M User s Manual REVO_M08 32 17 Electronic boards 17 1 How to access ...
Page 48: ...CD Automation srl REVO M User s Manual REVO_M08 48 ...