REVO C
2PH from 1100A to 2100A
User’s manual
19
6.4 Output features 690V
Current
Output
Voltage
range
(Ue)
Repetitive
peak
reverse
voltage
(Uimp)
Latching
current
Max peak
one cycle
Leakage
current
FUSE I2T
value
Suggested
A2s (at
660V)
Frequency
range
Power
loss
Thyristor
+ Fuse
FANS
(230Vac Standard)
(115Vac Option)
(A)
(V)
(up to
690V)
(mAeff)
(10msec.)
(A)
(mAeff) tp=10msec
(Hz)
I=Inom
(W)
N°
W
m3/h
1100A
24÷690
2200
700
36000
300
1.900.000
47÷70
2698
2
150
(75 x 2 Fan)
1560
(780 x 2 Fan)
1400A
24÷690
2200
700
36000
300
3.300.000
47÷70
3646
4
300
(75 x 4 Fan)
3120
(780 x 4 Fan)
1600A
24÷690
2200
700
36000
300
3.900.000
47÷70
3722
4
300
(75 x 4 Fan)
3120
(780 x 4 Fan)
1800A
24÷690
2200
700
60000
300
3.900.000
47÷70
4162
4
300
(75 x 4 Fan)
3120
(780 x 4 Fan)
2100A
24÷690
2200
700
60000
300
3.900.000
47÷70
4722
4
300
(75 x 4 Fan)
3120
(780 x 4 Fan)
6.5 Environmental installation conditions
Ambient temperature
0-40°C (32-104°F) at nominal current.
Over 40°C -104°F use the derating curve (max 50°C).
Storage temperature
-25°C to 70°C -13°F to 158°F
Installation place
Don’t install at direct sun light, where there are conductive
dust, corrosive gas, vibration or water and also
in salty environmental.
Altitude
Up to 1000 meter over sea level. For higher altitude
reduce the nominal current of 2% for each 100m over 1000m
Humidity
From 5 to 95% without condense and ice
Pollution Level
Up to 2nd Level ref. IEC 60947-1 6.1.3.2
6.6 Derating Curve and Thermal conditions
The nominal current of the units in specification are referred to continuous service at 40°C ambient temperature.
For higher temperature multiply the nominal current times derating coefficient K below represented:
l max = l nominal x K
1
15 20 25 30 35 40 45 50 55
1,2
1
0,8
0,6
0,4
0,2
0
1
1
1
1
0,9
0,8
K
CABINET TEMPERATURE °C
Derating
Operation at ambient operating temperature above 40°C not covered by UL
®
For higher cabinet
temperature
(more than 50°C)
contact the producer
of the unit