REVO C
2PH from 1100A to 2100A
User’s manual
69
12.2. AUX High
This alarm is displayed when the auxiliary supply voltage exceeds the established ranges. If the alarm situation
persists for more than 5 seconds, the unit will go into protection.
12.3 AUX Low
This alarm is displayed when the auxiliary supply voltage is lower than the established ranges.
This alarm condition could lead to incorrect unit operation.
12.4 ComError
If the communication watchdog function is enabled (watchdog ON) this alarm is activated when there is no
data passage within the time established by the “WD reset” parameter.
12.5 AUX Line Loss
This alarm is activated when there is no auxiliary voltage.
12.6 SD Error
When the Logging option is present, this alarm is activated when a writing error is found in the SD memory.
12.7 SHRT
This alarm is activated if the unit detects a short circuit in one of the power devices. This alarm could also
activate when the current measured by the unit is greater than 80% of the value set in Nominal I.
12.8 SCR Temp
This alarm is activated when the heat sink temperature exceeds the set threshold value (80°C).
12.9 Line Loss
This alarm is activated when L1 and L2 are not detected.
12.10 Phase Loss
This alarm is activated when L1 or L2 or L3 are not detected.
Summary of Contents for REVO C EXTENDED 2PH
Page 2: ......