REVO C
2PH from 1100A to 2100A
User’s manual
45
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
Pb Power
Set the gain for the main loop. A larger
value yields a larger adjustment for a
given deviation
10%
0 to 255
%
26
Read
Write
Ti Power
Set how aggressively the integral part
of the control algorithm acts. A larger
settings yields a larger adjustment for
a given deviation over a given time
50
0 to 255
27
Read
Write
HB Sense
Set the threshold of resistance that
activates the Heater Break alarm. This
setting is in percentage of the nominal
load resistance
100%
0 to 100.0
%
29
Read
Write
HB Delay
Set a delay between when the
resistance drops below the value set
for a heater break sensitivity and when
the heater break alarm is indicated.
This set increments of 50mSec
50
(2,5 sec)
0 to 255
(0 to 12,75
sec)
28
Read
Write
Logging
Enable or disable data logging on the
internal SD card
0
139
Read
Write
Option
Value
Off
0
On
1
DEFAULT:
Off
0
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
Log Period
Set how often data is logged
5 sec
0 to 255 sec
70
Read
Write