LSS-2404
11 |
P a g e
Selecting Power Supply
Choose a power supply that fulfills the requirements below
•
Well-regulated 12-24 VDC with appropriate current rating for attached lights (5V minimum)
•
Absolute voltage ratings are never exceeded in any installed operating conditions
o
Damage may occur if the input exceeds the specified absolute limits.
•
Total capacity at least equal to or greater than 100 mA PLUS the sum of all 4 channels of connected light
•
Note: 24V with 4.1A or greater can run the maximum allowed lighting
•
DO NOT USE power supplies with 10A capacity or larger
DO NOT USE THIS DEVICE WITH POWER SUPPLIES OR EXTERNAL COMPONENTS USING AN ISOLATED GROUND
SYSTEM THAT CANNOT BE CONNECTED TO AC GROUND. EXTERNAL COMPONENTS MUST SUPPORT A COMMON
GROUND SYSTEM.
To request configuration for use in floating or isolated ground systems,
please contact CCS America by sending
an email to
Ethernet Connection
Ethernet connectivity with TCP/IP protocol is standard on the 2404 controllers. The RJ45 Ethernet connector
requires a straight through cable to connect into a PC, network switch, hub or router. It operates at 100Mbits
per second (100 Base-T).
The IP address on the LSS-2404 is 192.168.0.10.