68
■
Switch setting
Fixing or Flexibility
Setting
Set Mode
SW4
SW5
SW1
SW2
F57(Min)
F58(Max)
Output
Current
4000
20000
4 – 20mA
0000
20000
0 – 20mA
Fixing 0 0 1 1
0000
24000
0 – 24mA
When you use the Fixing Mode (SW4=SW5=0),
you have to set one(1) of the SW1 & SW2 and
you have to set the values what you want to out in the SET MODE (F57 & F58)
Fixing or Flexibility
Setting
Set Mode
SW4
SW5
SW1
SW2
F57(Min)
F58(Max)
Output
Current
1
1
0 – 24mA
0
1
0 – 20mA
Flexibility 1 1
1 0
0000 24000
4 – 20mA
When you use the Flexibility Mode (SW4=SW5=1),
you select to set the setting switches what you want to out
If the output current is not correct, you need to adjust the volume resistors of VR1 & VR2.
VR1 is used to adjust to zero value. VR2 is used to adjust to Max. value.
SW1 SW2
Output
1
1
0 – 24mA
0
1
0 – 20mA
1
0
4 – 20mA