You can operate external control for your needs in user program control mode.
■
External input and output signal is as follows.
1. FIRST OUTPUT(Optional preliminary) :
It is ON when the gross weight is greater than optional preliminary weight.
It is OFF when the gross weight is lower than final weight.
- Fill in the hopper by using first output signal.
2. Press TARE key so that the display shows 0kg (NET weight).
3. SECOND OUTPUT(Preliminary) :
It is ON when the net weight is greater than the weight (Final - Preliminary).
4. THIRD OUTPUT(Final) :
It is ON when the NET weight is more than the weight (Final - Free fall).
5. HIGH LIMIT OUTPUT :
It is ON when the net weight is greater than the weight (Final + High limit)
after third output is ON.
6. LOW LIMIT OUTPUT :
It is ON when the net weight is greater than the weight (Final - Low limit)
after third output is ON.
7. FINISH SIGNAL :
When weight is stable, It is ON after passing the certain time of start delay
(You can set start delay time in set mode, F21.)
It is OFF after passing the certain time of operating delay or Finish Signal OFF
Range (F22). (You can set operating delay time in set mode, F19.)
8. ZERO BAND OUTPUT :
It is ON when the gross weight is lower than zero band value.
9. Discharge gate control signal is not supplied in CI-6000A.
- Use FINISH SIGNAL OUTPUT.
10. Prepare for next batching operation.
Summary of Contents for CI-6000A Series
Page 1: ...2 ...
Page 8: ...9 4 Measure of Appearance ...
Page 22: ...23 5 Sealing Method Sealing method of cal switch Sealing method of Load Cell Connector ...
Page 51: ...52 Normal Batching Diagram Loss in Weight Batching Diagram ...
Page 52: ...53 USER PROGRAM CONTROLMODE Normal Batching ...
Page 54: ...55 USER PROGRAM CONTROLMODE Loss in Weight ...
Page 56: ...57 AUTOMATIC PROGRAM CONTROLMODE Normal Batching ...
Page 58: ...59 AUTOMATIC PROGRAM CONTROLMODE Loss in Weight ...
Page 71: ...72 MEMO ...
Page 72: ...73 MEMO ...
Page 73: ...74 MEMO ...
Page 74: ...75 ...