Appendix A: VVT Zone II Points/Properties
VVT Zone II Controller
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
84
Point Name/Description
Default/Range
Effective Cool Setpoint
– The current cooling setpoint. May include offsets from
configured occupied/unoccupied setpoints resulting from
Optimal Start
to
Demand
Limit
.
R: _°F/C
Relative Humidity Source –
The source of the relative humidity value.
R: N/A
Local
Network
Linkage
Locked Value
ZS Sensor
IAQ Source –
The source of the indoor air quality value.
R: N/A
Local
Network
Linkage
Locked Value
ZS Sensor
Outdoor Air Temperature Source
– The source of the outdoor air temperature.
R: N/A
Local
Network
Linkage
Locked Value
Remaining Heat Delay –
If
Heat Delay
is
Active
, this is the remaining delay time.
R: 0 to 60 minutes
Cooling Demand Level
– The system cool demand level received over the network.
R: 0 to 3
Heating Demand Level
– The system heat demand level received over the network.
R: 0 to 3
Heat Delay –
The status of the terminal heat delay.
R: Inactive/Active
Remaining Heat Delay –
If
Heat Delay
is
Active
, this is the remaining delay time.
R: 0 to 60 minutes
Calculated DCV Damper Position –
If the controller is in IAQ Override mode, this is the
calculated minimum damper position that will be maintained to satisfy the mode.
R: 0 to 100%
Calculated Dehumidify Dmpr Position –
If the controller is in Dehumidify mode, this is
the calculated minimum damper position that will be maintained to satisfy the mode.
R: 0 to 100%
Reset Filter Alarm
– Set this to
On
to reset an active
Filter Alarm
and restart the
Filter
Service Alarm Timer
. After the alarm returns to normal, this automatically changes to
Off
.
D:
R:
Off
On/Off
Occupancy Contact State
- The physical state of the
Remote
input.
R: Open/Closed
Cooling BTU's
– Current Cooling Energy being delivered to the space.
R: 0 to 99999 BTU
(0 to 99999 KJoules)
Heating BTU's
– Current Heating Energy being delivered to the space.
R: 0 to 99999 BTU
(0 to 99999 KJoules)
Occupancy