Installing the VVT Zone II
VVT Zone II Controller
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
23
Wiring diagram for #33ZCT55CO2:
To wire the Relative Humidity sensor to the controller
Part #33ZCSENSRH-02
The Relative Humidity (RH) sensor is used for zone humidity control (dehumidification) if the rooftop unit has a
dehumidification device. If not, the sensor only monitors humidity.
NOTE
Do not use a relative humidity sensor and CO
2
sensor on the same zone controller.
1
Strip the outer jacket from the cable for at least 4 inches (10.2 cm). Strip .25 inch (.6 cm) of insulation from
each wire.
2
Wire the sensor to the controller. See diagram below.
3
Using electrical tape, insulate any exposed resistor lead to prevent shorting.
4
Verify that the
RH/CO2
jumper is set to
0-5 Vdc
.