Appendix D: BACnet points list
VVT Zone II Controller
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
97
BACnet
Point Name
Point
Access
Units
Default Value BACnet Point Name
BACnet Object ID
Cool Min Damper Position
R
%
cl_min_dmp_pos
Zone Type
R
1=Slave
2=VVT Master
3=VAV Master
zone_type
MSV:2008
Airside Linkage Status
R
0=Normal
1=Alarm
air_linkage_fail
BV:7030
Filter
R
0=Clean
1=Dirty
filter_alarm
BV:7017
High SPT
R
0=Normal
1=Alarm
spt_hi_alarm
BV:7011
Indoor Air Quality
R
0=Normal
1=Alarm
iaq_alarm
BV:7005
Low SPT
R
0=Normal
1=Alarm
spt_lo_alarm
BV:7012
Network OAT
R
0=Normal
1=Alarm
oat_fail
BV:7029
Space Relative Humidity
R
0=Normal
1=Alarm
sprh_hi_alarm
BV:7018
Space Temp Sensor
R
0=Normal
1=Alarm
spt_fail
BV:7001
Supply Air Temperature
R
0=Normal
1=Alarm
sat_alarm
BV:7004
Wireless Battery Strength Alarm
R
0=Normal
1=Alarm
ws_batt_alarm
BV:7064
Wireless Signal Strength Alarm
R
0=Normal
1=Alarm
ws_sig_alarm
BV:7065
ZS/WS Sensor Configuration
R
0=Normal
1=Alarm
zs_config_fail
BV:7055