To adjust the driver properties
VVT Zone II Controller
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
57
BACnet COV Throttling
Enable COV Throttling
Under normal circumstances, COV Throttling should be enabled to prevent
excessive network traffic if an object's COV Increment is set too low. See
EXCEPTION below.
When enabled, if an object generates excessive COV broadcasts (5 updates in 3
seconds), the driver automatically throttles the broadcasts to 1 per second. Also,
if the object's value updates excessively for 30 seconds, an alarm is sent to the i-
Vu® application listing all objects that are updating excessively. A Return-to-
normal alarm is sent only after all objects have stopped updating excessively.
EXCEPTION: In rare circumstances, such as process control, a subscribing object
may require COV updates more frequently than once per second. For these
situations, clear this checkbox, but make sure that your network can support the
increased traffic. You will also need to disable the
Excessive COV
alarms under
the driver's
Common Alarms
.
Trend Sampling
Collect a daily midnight
sample for all points in this
controller that are sampling
on COV
For values that change infrequently, select to verify at midnight daily that the
point is still able to communicate trend values.
Device
On the
Device
page, you can view the following properties:
•
BACnet device object properties for the VVT Zone II
•
VVT Zone II network communication
Configuration
NOTE
The three APDU fields refer to all networks over which the VVT Zone II
communicates.
Max Masters and Max Info
Frames
Apply only if the VVT Zone II is on an MS/TP network.
Summary of Contents for VVT Zone
Page 103: ......