Sequence of operation
VVT Zone II Controller
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
55
VENT
The zone’s local heat has not operated for at least 5 minutes and the SAT is
between 65 (18.3°C) and 80°F (26.6°C).
COOL
The zone’s local heat has not operated for at least 5 minutes, the current
mode is not Heat or Vent, and the SAT is less than 65°F (18.3°C).
See
Appendix B: VVT terminal modes
(page 92).