Appendix D: BACnet points list
VVT Zone II Controller
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
96
BACnet
Point Name
Point
Access
Units
Default Value BACnet Point Name
BACnet Object ID
Cool Min Damper Position
R
%
cl_min_dmp_pos
System Space Temperature
R/W
°F
-999
system_spt
AV:1902
Airside Linkage Status
R
0=Not Active
1=Active
a_link_status
BV:2601
DCV Control
R/W
0=Disable
1=Enable
Inactive (0)
dcv_enable
Fan
R
0=Off
1=On
sfan_status
BV:1003
Heat Enable
R/W
0=Disable
1=Enable
Active (1)
ht_enable
BV:1012
Occupancy Status
R
0=Unoccupied
1=Occupied
occ_status
BV:2008
Reset Filter Alarm
R/W
0=Off
1=On
Inactive (0)
filter_rntm_clr
BV:7517
RH Control
R/W
0=Disable
1=Enable
Inactive (0)
rh_enable
Setpoint Adjustment
R/W
0=Disable
1=Enable
Active (1)
stpt_adj_enable
BV:1013
Shutdown
R/W
0=Inactive
1=Active
Inactive (0)
shutdown
BV:9001
Air Source Mode
R
1=Off
2=Warmup
3=Heat
4=Cool
5=Freecool
6=Pressure
7=Evac
8=Vent
link_ahu_mode
MSV:2005
BAS On / Off
R/W
1=Inactive
2=Occupied
3=Unoccupied
1
keypad_ovrde
MSV:1001
Optimal Start Type
R/W
1=None
2=Temp
Compensated
3=Learning Adaptive
2
start_type
MSV:2009
Space Temp Source
R
1=Sensor Failure
2=SPT Sensor
3=T55 / T56
4=Network
5=Airside Linkage
6=Locked Value
7=ZS Sensor
8=Wireless Sensor
spt_status
MSV:2003
Terminal Mode
R
1=Off
2=Heating
3=Warm-Up
4=Vent
5=N/A
6=Cooling
7=Dehumidify
8=Reheat
9=Pressurize
10=Evacuate
11=Shutdown
12=IAQ Override
13=Air Balancing
terminal_status
MSV:2006
Terminal Type
R
1=Single Duct
2=Parallel Fan
3=Series Fan
terminal_type
MSV:2007