SMOKE DETECTOR/FIRE ALARM SHUTDOWN (FSD)
(PCB1) — To allow a smoke detector to shut the unit down,
remove the jumper from terminal block J4, terminals 19 and 20
and wire these terminals to a set of normally closed contacts on
the smoke detector.
ALARM (ALARM) OUTPUT (PCB1) — A Form C dry
contact is provided to signal when the controller has an active
alarm. To use these for remote annunciation, connect wiring to
terminal block J10, terminal 18 (normally open), terminal 17
(common), and/or terminal 16 (normally closed).