background image

5

economizer coil or heating coil, is a factory-installed  averag-

ing air temperature sensor positioned in the unit inlet airstream.

This may be either a thermistor sensor (automatic reset) or a

switch with capillary tube (manual reset). The unit activates

freeze protection when the sensed air temperature falls below

37 F. In freeze conditions, the supply fan will be stopped, all

compressors will stop, the economizer valve will open to

100%, the pump request output will remain on, and the alarm

lamp will light. This will maintain condenser water flow

through the coil to prevent freezing the coil while stopping all

other operations that could have contributed or will be affected

by the freeze condition. Unit reset is automatic when the con-

tacts on the freeze protection switch close again OR when the

thermistor sensed air temperature exceeds 42 F.
TOWER SUMP TEMPERATURE SENSOR (PCB2) —

This field sensor is used for monitoring (only) the tower sump

temperature.
LEAVING WATER TEMPERATURE SENSOR

(PCB2) — This sensor is used only for monitoring the leaving

water temperature.
BUILDING STATIC PRESSURE SENSOR (PCB1) —

This sensor is used to control the speed of the building exhaust

fan to maintain the building static pressure.
BUILDING EXHAUST FAN SPEED CONTROL

(PCB1) — This output controls building exhaust fan speed.
INDOOR AIR QUALITY (CO

2

) SENSOR (PCB1) — This

sensor monitors CO

2

 levels and is used to provide demand ven-

tilation override with an air economizer.
OUTDOOR AIR TEMPERATURE SENSOR (PCB2) —

This sensor is used to monitor outdoor-air temperature. When

an air economizer is installed, this is used for changeover and

lockout.
INDOOR RELATIVE HUMIDITY SENSOR (PCB1) —

This sensor monitors the indoor relative humidity and controls

the humidity control relay.
HUMIDITY CONTROL RELAY (PCB2, DEHUMID-

IFY) — This relay controls a humidifier or dehumidification

device.

Wiring Control Devices — 

Standard controls for the

50XJ unit require no field wiring. Standard 50XJ controls in-

clude: supply-air temperature (SAT), duct static pressure

(DSP), duct high static limit switch (DHS), compressor status

relays (CRx), supply fan control (BPS_S and/or VFD), and

mixed-air/return-air sensor (MA_RA). 
NOTE: The MA_RA sensor will be located in the return

airsteam if the unit does not have a water economizer, and in

the mixed airstream if the unit is equipped with a water

economizer.
EXTERNAL 0 TO 10 VOLT DC RESET SIGNAL (RESET,

PCB1) — This field-supplied 0 to 10 vdc signal is used to reset

the supply-air temperature. The controller will scale the signal

to provide 0 reset at 0 volts and 20 degrees of reset at 10 volts.

Wire the positive of the signal to controller terminal block J4,

terminal 16 and the negative to terminal 17.
SUPPLY AIR RESET BY SPACE TEMPERATURE —   Use

a 10K-type II thermistor sensor installed at the entering water

temperature sensor location on PCB2 and configure the unit to

control reset by the entering water temperature sensor OR use

the normal space temperature sensor as described below. These

sensors may be connected in a series-parallel network in the

same manner as the space temperature sensor.
SPACE TEMPERATURE SENSOR (PCB1) — The  space

temperature sensor (33ZCT55SPT) is used in the following

cases:
• When using the optional water economizer

• To determine the average temperature of the space

served

• To determine supply-air temperature reset, occupied

heating, unoccupied heating and cooling (refer to

Sequence of Operation in Operation section).
To wire the sensor, perform the following (see Fig. 1).

1. Identify which cable is for the sensor wiring.
2. Strip back the jacket from the cable for at least 3 inches.

Strip 

1

/

4

-in. of insulation from each conductor. Cut the

shield and drain wire from the sensor end of the cable.

3. Wire the sensor to controller terminal block J4, terminals

9 and 10. A typical 10K thermistor such as the

33ZCT55SPT sensor may be used. If the SPT sensor is

not installed and the MA_RA (mixed air/return air) sen-

sor is configured for return air, the 50XJ unit will use this

sensor to control supply air reset, occupied heat, and un-

occupied heating and cooling. See Fig. 2 for space tem-

perature sensor averaging.

HOT WATER OR STEAM VALVE (HWV, PCB1) —   The

controller supplies a 0 to 10 vdc control signal for hot water or

steam valve control or electric heat control in occupied and un-

occupied heat modes. A field-installed step sequencer is re-

quired to convert this signal into 2, 4 or other stages of electric

heat. The positive signal is on terminal block J9, terminal 7,

with the signal common (negative) on terminal 8.

AIR TERMINALS AND FRESH AIR DAMPER

(PCB2) — The VAV terminal open (TRMOP), ventilation out-

put (VENTR), VAV terminal control (TRMCT), and heat inter-

lock relay (HIR) terminals provide dry contacts to command

the VAV terminals open; a ventilation damper open; VAV ter-

minals to control to their cooling set points; and VAV terminals

to control to their heat set points, respectively. These contacts

are located on terminal block J5: TRMOP terminals 7 and 8,

VENTR terminals 5 and 6, TRMCT terminals 3 and 4, and

HIR terminals 1 and 2.
REMOTE OCCUPANCY (PCB1) — The unit may be com-

manded by a remote control system or a twist timer to become

occupied and run when a set of dry contacts close. To enable

remote occupancy control, configure the occupancy point in

BACview to "remote (DI) on/off" and wire the remote contacts

to terminal block J4, terminals 17 and 18.

2

3

4

5

6

1

SW1

SEN

BRN (GND)

BLU (SPT)

RED(+)

WHT(GND)

BLK(-)

CCN COM

SENSOR WIRING

Fig. 1 — Space Temperature Sensor

Typical Wiring (33ZCT55SPT)

a33-675ef

Summary of Contents for OMNIZONE 50XJ104

Page 1: ...n working on this equipment observe precautions in the literature on tags stickers and labels attached to the equip ment and any other safety precautions that apply Follow all safety codes Wear safety...

Page 2: ...tion Optional and Field Installed Accessory Sensors Devices These units can be ordered with options and ac cessories that add functionality and control These options and accessories are used as descri...

Page 3: ...og 5K Sensor IN 10 W8 Therm Dry Water Econ Freezestat Sensor or Switch FREEZE Analog 10K 2 Sensor or Switch Closure IN 11 IW7 Therm Dry configurable Mixed Return Air Temperature MA_RA Analog 10K 2 Sen...

Page 4: ...signal 1 to 5 vdc linearly The sensor s range is 0 to 550 psig Water Valve s Control Variable Building Waterflow Systems Variable waterflow configurations use only one water valve in the main water su...

Page 5: ...l 16 and the negative to terminal 17 SUPPLY AIR RESET BY SPACE TEMPERATURE Use a 10K type II thermistor sensor installed at the entering water temperature sensor location on PCB2 and configure the uni...

Page 6: ...e for remote annunciation connect wiring to terminal block J10 terminal 18 normally open terminal 17 common and or terminal 16 normally closed J4 9 10 RED BLK RED RED BLK BLK BLK RED BLK RED SENSOR 1...

Page 7: ...t digital input such as duct high limit switch When the jumper is in the top position the input is configured for a voltage input for example a humidity sensor The bottom jumper position is used for m...

Page 8: ...50 60 Hz 20VA 0 83A Use Copper Conductors Only 232 EIA EIA 485 Port 1 Port 2a Therm Dry Unused 5 6 7 8 Network Switches 0 off 1 on MSTP m MSTP s PTP SLTA PlugIn Ethernet 8 7 6 5 Protocol 0 0 0 0 0 0...

Page 9: ...If the standby screen is visible press any key to switch to the HOME menu 2 If another screen is displayed press the HOME to switch to the HOME menu 3 Press the LOGOUT softkey to force the system to...

Page 10: ...ompressor start stop test This is the same test point used to test the VFD bypass Since constant volume units do not have remote VAV termi nals there is no built in delay to allow remote boxes to open...

Page 11: ...es Local schedules are one method of starting and stopping the unit at specified intervals There are four normal schedules that provide day to day opera tion There are twelve holiday schedules that ar...

Page 12: ...ule When an override schedule is active it overrides any nor mal or holiday schedule and forces the unit to occupied mode In the example listed under the holiday schedule assume an override schedule...

Page 13: ...runtime limits or clear the accumulated run times To view run times press the CONFIG softkey on the HOME menu then select the RUNTIME option from the CONFIGURATION menu Use the arrow keys to scroll th...

Page 14: ...entry press EXIT and re start the procedure at Step 6 9905 Motor Nom Volt should equal unit voltage 230V or 460V 9906 Motor Nom Current equal to motor FLA see motor nameplate 9907 Motor Nom Freq alwa...

Page 15: ...elp screens START UP WITH ASSISTANT To start up the VFD with the Start Up Assistant perform the following proce dure 1 Select MENU SOFT KEY 2 The Main menu will be displayed 2 Use the UP or DOWN keys...

Page 16: ...and then press EXIT SOFT KEY 1 to return to main menu NOTE The current parameter value appears above the highlight parameter To view the default parameter value press the UP and DOWN keys simultaneous...

Page 17: ...not be changed 6 Press EXIT SOFT KEY 1 twice to return to the main menu START UP General Complete the start up checklist on page CL 1 before attempting system start up Confirm that compressor suction...

Page 18: ...of these sensors in the custom configuration The following sensors when valid are used for the space tempera ture sensor with the highest precedence at the top of the list Space temperature sensor SPT...

Page 19: ...e 65 F HEAD PRESSURE CONTROL HPC In installations where entering water temperature can fall below 55 F where a water economizer described above is not installed the HPC provides an electronic water fl...

Page 20: ...of each compressor and is set to open at pressures above 570 psig It is wired in the 24 vac control power line of the compressor contactor in series with the LPS and FRZ and disables compressor operat...

Page 21: ...he compres sor and attempt to restart it 15 minutes later assuming there is still a call for cooling On a third failed attempt to run the compressor the compressor will be locked out pending a pow er...

Page 22: ...r control of an air economizer OUTDOOR AIR TEMPERATURE ALARM OAT If an outdoor air temperature sensor is installed and configured an alarm with an ID of oat_alarm will be generated if the temperature...

Page 23: ...ISC1 Disconnect Switch DSP Duct Static Pressure Transducer ECONO Economizer Valve Damper Control EWT Entering Water Temperature Sensor FLTS Filter Status Switch FREEZ Freeze Thermostat Water Economize...

Page 24: ...3 L1 T1 L2 T2 L3 T3 FU10 FU11 FU12 COMP3 151 BLK 157 BLU 154 YEL 150 BLK 156 BLU 153 YEL 149 BLK 155 BLU 152 YEL C3 158 BLK 159 BLK CH3 2 1 3 L2 T2 L3 T3 FU13 FU14 FU15 COMP4 162 BLK 168 BLU 165 YEL 1...

Page 25: ...Z2 409 PNK 408 PNK 407 PNK 406 PNK LPS2 400 BLU 534 BLU HPS1 FRZ1 404 BLU 403 BLU 402 BLU 401 BLU LPS1 TB5 531 BRN 528 BRN 525 BRN 522 BRN 532 BRN 427 BRN 433 BRN 432 BRN 430 BRN 428 BRN 429 BRN 431 B...

Page 26: ...tion PUMP REQUEST FIELD Connection TOWER REQUEST FIELD Connection EXT DEHUMIDIFY Tower Sump Leaving Water 627 ORN 628 BLU 629 BRN FIELD Connection TRMOP FIELD Connection VENTR FIELD Connection TRMCT F...

Page 27: ...701 GRN 630 ORN 631 VIO HRN3 4 3 FIELD Connection Exhaust Fan DSP 640 BLK A B BPS_S 617 BRN 6 5 638 BRN 638 BRN 627 ORN 628 BLU 629 BRN 603 RED 606 BRN 639 RED 607 RED 609 RED 611 RED 613 RED FIELD A...

Page 28: ......

Page 29: ......

Page 30: ...right to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500117 01 Printed in U S A Form 50XJ 2T Pg 30 8 14 Replaces 50XJ 1...

Page 31: ...INPUT POWER PHASE SEQUENCE BEEN CONFIRMED WITH A METER Y N _______ HAS THE FAN AND MOTOR PULLEY BEEN CHECKED FOR PROPER ALIGNMENT AND DOES THE FAN BELT HAVE PROPER TENSION Y N _______ HAS WATER BEEN P...

Page 32: ..._____________________________________________________________________________________________ _______________________________________________________________________________________________ __________...

Reviews: