Carrier OMNIZONE 50XJ104 Controls, Start-Up, Operation And Troubleshooting Download Page 22

22

be generated. This error disables tenant (unoccupied) override

by the SPT sensor and prevents use of this sensor value in the

cooling/heating mode determination and the supply air reset

calculation.
ENTERING WATER TEMPERATURE ALARM

(EWT) — If an entering water temperature sensor is installed

or the unit is configured for supply air temperature reset by the

entering water temperature input, an alarm with an ID of

"ewt_alarm" will be generated if the temperature input exceeds

115 F or falls below 35 F. The alarm output will close and the

red alarm lamp will be lit; however, this alarm does not affect

unit operation.
ENTERING WATER TEMPERATURE SENSOR FAIL-

URE (EWT)  — If an entering water temperature sensor is in-

stalled or the unit is configured for supply air temperature reset

by the entering water temperature input, an alarm with an ID of

"ewt_sen_alarm" will be generated if the temperature input ex-

ceeds 200 F or falls below -45 F. The alarm output will close

and the red alarm lamp will light. The EWT output will show

0

°

 F and this sensor should not be used in the cooling/heating

mode determination or the supply air reset calculation (if en-

abled). This alarm will also disable water economizer opera-

tion and head pressure control.
MIXED OR RETURN AIR TEMPERATURE ALARM

(MA_RA) — If a mixed or return air temperature sensor is in-

stalled, an alarm with an ID of "mara_alarm" will be generated

if the temperature input exceeds 120 F or falls below 35 F. The

alarm output will close and the red alarm lamp will light; how-

ever, this alarm does not affect unit operation.
MIXED OR RETURN AIR TEMPERATURE SENSOR

FAILURE (MA_RA) — If a mixed or return air temperature

sensor is installed, an alarm with an ID of "mara_sen_alarm"

will be generated if the temperature input exceeds 200 F or

falls below -45 F. The alarm output will close, the red alarm

lamp will light, and the unit will output a value of 0

°

 F for this

point. This invalid input is not used the supply air reset calcula-

tion, cooling/heating mode determination, or for control of an

air economizer.
OUTDOOR AIR TEMPERATURE ALARM (OAT) —   If

an outdoor air temperature sensor is installed and configured,

an alarm with an ID of "oat_alarm" will be generated if the

temperature input exceeds 120 F or falls below 35 F. The alarm

output will close and the red alarm lamp will light; however,

this alarm does not affect unit operation.
OUTDOOR AIR TEMPERATURE SENSOR FAILURE

(OAT) — If an outdoor air temperature sensor is installed and

configured, an alarm with an ID of "oat_alarm" will be gener-

ated if the temperature input exceeds 200 F or falls below

-45 F. The alarm output will close and the red alarm lamp will

light. The outside air temperature output will show 0

°

 F and the

program will use a value of (Economizer Se 2 F) for

the outside-air temperature in the optional airside economizer

routine.
COMPRESSOR RUNTIME ALARM — There is a set point

to define a maximum compressor runtime in hours for each

compressor. If a non-zero value is entered, the unit will gener-

ate an alarm with an ID of "dx#_rntm" when the compressor

runtime exceeds the set point.  "#" designates the compressor

number. This alarm will cause the red alarm lamp to be lit, but

since it is only a status alarm, unit operation is not affected and

this does not close the alarm output.
SUPPLY FAN RUNTIME ALARM — There is a set point

to define a maximum supply fan run time. If a non-zero value

is entered, the unit will generate an alarm with an ID of

"sf_rntm" when the runtime exceeds the set point. This alarm

will cause the red alarm lamp to be lit, but since it is only a sta-

tus alarm, unit operation is not affected and this does not close

the alarm output.
SELF-TEST ALARM — When the user starts a self-test se-

quence, an alarm with an ID of "selftest_alarm" will be gener-

ated and the red alarm lamp will light. This alarm is maintained

for 4 minutes after the last self-test sequence has run. This

alarm stops normal unit operation, but the unit returns to nor-

mal operation when the alarm is cleared. The alarm output is

closed to designate each step of multi-step self-test routines

(see the Automatic Self-Test section for details).

50XJ Wiring Diagrams  — 

The typical wiring diagrams

for the 50XJ units are shown in Fig. 11 and 12.

Summary of Contents for OMNIZONE 50XJ104

Page 1: ...n working on this equipment observe precautions in the literature on tags stickers and labels attached to the equip ment and any other safety precautions that apply Follow all safety codes Wear safety...

Page 2: ...tion Optional and Field Installed Accessory Sensors Devices These units can be ordered with options and ac cessories that add functionality and control These options and accessories are used as descri...

Page 3: ...og 5K Sensor IN 10 W8 Therm Dry Water Econ Freezestat Sensor or Switch FREEZE Analog 10K 2 Sensor or Switch Closure IN 11 IW7 Therm Dry configurable Mixed Return Air Temperature MA_RA Analog 10K 2 Sen...

Page 4: ...signal 1 to 5 vdc linearly The sensor s range is 0 to 550 psig Water Valve s Control Variable Building Waterflow Systems Variable waterflow configurations use only one water valve in the main water su...

Page 5: ...l 16 and the negative to terminal 17 SUPPLY AIR RESET BY SPACE TEMPERATURE Use a 10K type II thermistor sensor installed at the entering water temperature sensor location on PCB2 and configure the uni...

Page 6: ...e for remote annunciation connect wiring to terminal block J10 terminal 18 normally open terminal 17 common and or terminal 16 normally closed J4 9 10 RED BLK RED RED BLK BLK BLK RED BLK RED SENSOR 1...

Page 7: ...t digital input such as duct high limit switch When the jumper is in the top position the input is configured for a voltage input for example a humidity sensor The bottom jumper position is used for m...

Page 8: ...50 60 Hz 20VA 0 83A Use Copper Conductors Only 232 EIA EIA 485 Port 1 Port 2a Therm Dry Unused 5 6 7 8 Network Switches 0 off 1 on MSTP m MSTP s PTP SLTA PlugIn Ethernet 8 7 6 5 Protocol 0 0 0 0 0 0...

Page 9: ...If the standby screen is visible press any key to switch to the HOME menu 2 If another screen is displayed press the HOME to switch to the HOME menu 3 Press the LOGOUT softkey to force the system to...

Page 10: ...ompressor start stop test This is the same test point used to test the VFD bypass Since constant volume units do not have remote VAV termi nals there is no built in delay to allow remote boxes to open...

Page 11: ...es Local schedules are one method of starting and stopping the unit at specified intervals There are four normal schedules that provide day to day opera tion There are twelve holiday schedules that ar...

Page 12: ...ule When an override schedule is active it overrides any nor mal or holiday schedule and forces the unit to occupied mode In the example listed under the holiday schedule assume an override schedule...

Page 13: ...runtime limits or clear the accumulated run times To view run times press the CONFIG softkey on the HOME menu then select the RUNTIME option from the CONFIGURATION menu Use the arrow keys to scroll th...

Page 14: ...entry press EXIT and re start the procedure at Step 6 9905 Motor Nom Volt should equal unit voltage 230V or 460V 9906 Motor Nom Current equal to motor FLA see motor nameplate 9907 Motor Nom Freq alwa...

Page 15: ...elp screens START UP WITH ASSISTANT To start up the VFD with the Start Up Assistant perform the following proce dure 1 Select MENU SOFT KEY 2 The Main menu will be displayed 2 Use the UP or DOWN keys...

Page 16: ...and then press EXIT SOFT KEY 1 to return to main menu NOTE The current parameter value appears above the highlight parameter To view the default parameter value press the UP and DOWN keys simultaneous...

Page 17: ...not be changed 6 Press EXIT SOFT KEY 1 twice to return to the main menu START UP General Complete the start up checklist on page CL 1 before attempting system start up Confirm that compressor suction...

Page 18: ...of these sensors in the custom configuration The following sensors when valid are used for the space tempera ture sensor with the highest precedence at the top of the list Space temperature sensor SPT...

Page 19: ...e 65 F HEAD PRESSURE CONTROL HPC In installations where entering water temperature can fall below 55 F where a water economizer described above is not installed the HPC provides an electronic water fl...

Page 20: ...of each compressor and is set to open at pressures above 570 psig It is wired in the 24 vac control power line of the compressor contactor in series with the LPS and FRZ and disables compressor operat...

Page 21: ...he compres sor and attempt to restart it 15 minutes later assuming there is still a call for cooling On a third failed attempt to run the compressor the compressor will be locked out pending a pow er...

Page 22: ...r control of an air economizer OUTDOOR AIR TEMPERATURE ALARM OAT If an outdoor air temperature sensor is installed and configured an alarm with an ID of oat_alarm will be generated if the temperature...

Page 23: ...ISC1 Disconnect Switch DSP Duct Static Pressure Transducer ECONO Economizer Valve Damper Control EWT Entering Water Temperature Sensor FLTS Filter Status Switch FREEZ Freeze Thermostat Water Economize...

Page 24: ...3 L1 T1 L2 T2 L3 T3 FU10 FU11 FU12 COMP3 151 BLK 157 BLU 154 YEL 150 BLK 156 BLU 153 YEL 149 BLK 155 BLU 152 YEL C3 158 BLK 159 BLK CH3 2 1 3 L2 T2 L3 T3 FU13 FU14 FU15 COMP4 162 BLK 168 BLU 165 YEL 1...

Page 25: ...Z2 409 PNK 408 PNK 407 PNK 406 PNK LPS2 400 BLU 534 BLU HPS1 FRZ1 404 BLU 403 BLU 402 BLU 401 BLU LPS1 TB5 531 BRN 528 BRN 525 BRN 522 BRN 532 BRN 427 BRN 433 BRN 432 BRN 430 BRN 428 BRN 429 BRN 431 B...

Page 26: ...tion PUMP REQUEST FIELD Connection TOWER REQUEST FIELD Connection EXT DEHUMIDIFY Tower Sump Leaving Water 627 ORN 628 BLU 629 BRN FIELD Connection TRMOP FIELD Connection VENTR FIELD Connection TRMCT F...

Page 27: ...701 GRN 630 ORN 631 VIO HRN3 4 3 FIELD Connection Exhaust Fan DSP 640 BLK A B BPS_S 617 BRN 6 5 638 BRN 638 BRN 627 ORN 628 BLU 629 BRN 603 RED 606 BRN 639 RED 607 RED 609 RED 611 RED 613 RED FIELD A...

Page 28: ......

Page 29: ......

Page 30: ...right to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500117 01 Printed in U S A Form 50XJ 2T Pg 30 8 14 Replaces 50XJ 1...

Page 31: ...INPUT POWER PHASE SEQUENCE BEEN CONFIRMED WITH A METER Y N _______ HAS THE FAN AND MOTOR PULLEY BEEN CHECKED FOR PROPER ALIGNMENT AND DOES THE FAN BELT HAVE PROPER TENSION Y N _______ HAS WATER BEEN P...

Page 32: ..._____________________________________________________________________________________________ _______________________________________________________________________________________________ __________...

Reviews: