Table 1 — Control Inputs and Outputs

                   

LEGEND

DESCRIPTION

ABBREV.

TYPE

I/O NO.

JUMPER SETTINGS

INPUTS
MAIN CONTROLLER (PCB1)

Aux. Pwr Out: 24V

 Refrigerant Pressure (Cir. no. 1)

PRES

0-5V; Internally Powered

UI-01

IN01: 0-10V

 Duct Static Pressure

DSP

4-20mA; Internally Powered

UI-02

IN02: 0-20mA

 Duct High Static Limit Switch

DHS

Switch Closure

UI-03

IN03: RTD/Dry/Therm

 Supply Air Temperature

SAT

Analog; 10K-2 Sensor 

UI-04

IN04: RTD/Dry/Therm

 unassigned

UI-05

IN05: RTD/Dry/Therm

 Space Zone Sensor (analog)

SPT

Analog; 10K-2 Sensor

UI-06

IN06: RTD/Dry/Therm

 Indoor Air Quality

IAQ

Analog; 0-10V,Ext Powered

UI-07

IN07: 0-10V

 Indoor Relative Humidity

IRH

Analog; 0-10V,Ext Powered

UI-08

IN08: 0-10V

 Building Static Pressure

BSP

Analog; 0-10V,Ext Powered

UI-09

IN09: 0-10V

 External Reset

RESET

Analog; 0-10V,Ext Powered

UI-10

IN10: 0-10V

 Remote Occupancy

RMTOCC

Switch Closure

UI-11

IN11: RTD/Dry/Therm

 Fire Alarm/Shutdown

FSD

Switch Closure

UI-12

IN12: RTD/Dry/Therm

I/O BOARD (PCB2)
 Compressor 1 Status

CR1

Switch Closure

IN-01

 Compressor 2 Status

CR2

Switch Closure

IN-02

 Compressor 3 Status

CR3

Switch Closure

IN-03

 Compressor 4 Status

CR4

Switch Closure

IN-04

 Condenser Water Flow Switch

CDWF

Switch Closure

IN-05

 Phase/Rotation Monitor

PHASE

Switch Closure

IN-06

 Filter Status Switch (Dirty Filter Detect)

FLTS

Switch Closure

IN-07

 Differential Enthalpy

ENTH

Switch Closure

IN-08

 unassigned

IN-09

IW9:Therm/Dry

 Entering Water Temperature

EWT

Analog; 5K Sensor

IN-10

W8:Therm/Dry

 Water Econ Freezestat Sensor or Switch

FREEZE

Analog; 10K-2 Sensor or Switch Closure IN-11

IW7:Therm/Dry (configurable)

 Mixed/Return Air Temperature

MA_RA

Analog; 10K-2 Sensor

IN-12

IW6:Therm/Dry

 Tower Sump Temperature

TWRTEMP

Analog; 10K-2 Sensor

IN-13

IW5:Therm/Dry

 Leaving Water Temperature

LWT

Analog; 10K-2 Sensor

IN-14

IW4:Therm/Dry

 Outdoor Air Temperature

OAT

Analog; 10K-2 Sensor

IN-15

IW2:Therm/Dry

 unassigned

IN-16

IW1:Therm/Dry

BINARY OUTPUTS
MAIN CONTROLLER (PCB1)
 Compressor 1

Relay; Form C

BO-01

 Compressor 1

Relay; Form C

BO-02

 Compressor 1

Relay; Form C

BO-03

 Compressor 1

Relay; Form C

BO-04

 VFD Bypass Start/Stop or CV Fan Start/Stop

BPS_S

Relay; Form C 

BO-05

 Field Alarm Connection

Alarm

Relay; Form C

BO-06

Field Use

 I/O Board (PCB2)
 Heat Interlock Relay

HIR

Relay; Form A (N.O.)

BO-01

 VAV Terminal Control

TRMCT

Relay; Form A (N.O.)

BO-02

 Ventilation Output

VENTR

Relay; Form A (N.O.)

BO-03

 VAV Terminal Open

TRMOP

Relay; Form A (N.O.)

BO-04

 Water Pump Request

PUMP

Relay; Form A (N.O.)

BO-05

 Tower Request

TOWER

Relay; Form A (N.O.)

BO-06

 External Humidify/Dehumidify

HUMID_OUT

Relay; Form A (N.O.)

BO-07

 unassigned

Relay; Form A (N.O.)

BO-08

ANALOG OUTPUTS
MAIN CONTROLLER (PCB1)
 VFD Speed Control

VFD

0-10V

AO-1

 Modulating Valve Econ./Head Pressure 
Control

MVLV

0-10V

AO-2

 2-Position/Reverse Operation
Valve or Air Economizer

ECONO

0-10V

AO-3

 Heating Output

HEAT

0-10V

AO-4

 Modulating Exhaust Fan

EXH

0-10V

AO-5

 unassigned

0-10V

AO-6

AO

Analog Output

BO

Binary Output

CV

Constant Volume

I/O

Input/Output

N.O.

Normally Open

RTD

Resistance Temperature Detector

VAV

Variable Air Volume

VFD

Variable Frequency Drive

Summary of Contents for OMNIZONE 50XJ104

Page 1: ...n working on this equipment observe precautions in the literature on tags stickers and labels attached to the equip ment and any other safety precautions that apply Follow all safety codes Wear safety...

Page 2: ...tion Optional and Field Installed Accessory Sensors Devices These units can be ordered with options and ac cessories that add functionality and control These options and accessories are used as descri...

Page 3: ...og 5K Sensor IN 10 W8 Therm Dry Water Econ Freezestat Sensor or Switch FREEZE Analog 10K 2 Sensor or Switch Closure IN 11 IW7 Therm Dry configurable Mixed Return Air Temperature MA_RA Analog 10K 2 Sen...

Page 4: ...signal 1 to 5 vdc linearly The sensor s range is 0 to 550 psig Water Valve s Control Variable Building Waterflow Systems Variable waterflow configurations use only one water valve in the main water su...

Page 5: ...l 16 and the negative to terminal 17 SUPPLY AIR RESET BY SPACE TEMPERATURE Use a 10K type II thermistor sensor installed at the entering water temperature sensor location on PCB2 and configure the uni...

Page 6: ...e for remote annunciation connect wiring to terminal block J10 terminal 18 normally open terminal 17 common and or terminal 16 normally closed J4 9 10 RED BLK RED RED BLK BLK BLK RED BLK RED SENSOR 1...

Page 7: ...t digital input such as duct high limit switch When the jumper is in the top position the input is configured for a voltage input for example a humidity sensor The bottom jumper position is used for m...

Page 8: ...50 60 Hz 20VA 0 83A Use Copper Conductors Only 232 EIA EIA 485 Port 1 Port 2a Therm Dry Unused 5 6 7 8 Network Switches 0 off 1 on MSTP m MSTP s PTP SLTA PlugIn Ethernet 8 7 6 5 Protocol 0 0 0 0 0 0...

Page 9: ...If the standby screen is visible press any key to switch to the HOME menu 2 If another screen is displayed press the HOME to switch to the HOME menu 3 Press the LOGOUT softkey to force the system to...

Page 10: ...ompressor start stop test This is the same test point used to test the VFD bypass Since constant volume units do not have remote VAV termi nals there is no built in delay to allow remote boxes to open...

Page 11: ...es Local schedules are one method of starting and stopping the unit at specified intervals There are four normal schedules that provide day to day opera tion There are twelve holiday schedules that ar...

Page 12: ...ule When an override schedule is active it overrides any nor mal or holiday schedule and forces the unit to occupied mode In the example listed under the holiday schedule assume an override schedule...

Page 13: ...runtime limits or clear the accumulated run times To view run times press the CONFIG softkey on the HOME menu then select the RUNTIME option from the CONFIGURATION menu Use the arrow keys to scroll th...

Page 14: ...entry press EXIT and re start the procedure at Step 6 9905 Motor Nom Volt should equal unit voltage 230V or 460V 9906 Motor Nom Current equal to motor FLA see motor nameplate 9907 Motor Nom Freq alwa...

Page 15: ...elp screens START UP WITH ASSISTANT To start up the VFD with the Start Up Assistant perform the following proce dure 1 Select MENU SOFT KEY 2 The Main menu will be displayed 2 Use the UP or DOWN keys...

Page 16: ...and then press EXIT SOFT KEY 1 to return to main menu NOTE The current parameter value appears above the highlight parameter To view the default parameter value press the UP and DOWN keys simultaneous...

Page 17: ...not be changed 6 Press EXIT SOFT KEY 1 twice to return to the main menu START UP General Complete the start up checklist on page CL 1 before attempting system start up Confirm that compressor suction...

Page 18: ...of these sensors in the custom configuration The following sensors when valid are used for the space tempera ture sensor with the highest precedence at the top of the list Space temperature sensor SPT...

Page 19: ...e 65 F HEAD PRESSURE CONTROL HPC In installations where entering water temperature can fall below 55 F where a water economizer described above is not installed the HPC provides an electronic water fl...

Page 20: ...of each compressor and is set to open at pressures above 570 psig It is wired in the 24 vac control power line of the compressor contactor in series with the LPS and FRZ and disables compressor operat...

Page 21: ...he compres sor and attempt to restart it 15 minutes later assuming there is still a call for cooling On a third failed attempt to run the compressor the compressor will be locked out pending a pow er...

Page 22: ...r control of an air economizer OUTDOOR AIR TEMPERATURE ALARM OAT If an outdoor air temperature sensor is installed and configured an alarm with an ID of oat_alarm will be generated if the temperature...

Page 23: ...ISC1 Disconnect Switch DSP Duct Static Pressure Transducer ECONO Economizer Valve Damper Control EWT Entering Water Temperature Sensor FLTS Filter Status Switch FREEZ Freeze Thermostat Water Economize...

Page 24: ...3 L1 T1 L2 T2 L3 T3 FU10 FU11 FU12 COMP3 151 BLK 157 BLU 154 YEL 150 BLK 156 BLU 153 YEL 149 BLK 155 BLU 152 YEL C3 158 BLK 159 BLK CH3 2 1 3 L2 T2 L3 T3 FU13 FU14 FU15 COMP4 162 BLK 168 BLU 165 YEL 1...

Page 25: ...Z2 409 PNK 408 PNK 407 PNK 406 PNK LPS2 400 BLU 534 BLU HPS1 FRZ1 404 BLU 403 BLU 402 BLU 401 BLU LPS1 TB5 531 BRN 528 BRN 525 BRN 522 BRN 532 BRN 427 BRN 433 BRN 432 BRN 430 BRN 428 BRN 429 BRN 431 B...

Page 26: ...tion PUMP REQUEST FIELD Connection TOWER REQUEST FIELD Connection EXT DEHUMIDIFY Tower Sump Leaving Water 627 ORN 628 BLU 629 BRN FIELD Connection TRMOP FIELD Connection VENTR FIELD Connection TRMCT F...

Page 27: ...701 GRN 630 ORN 631 VIO HRN3 4 3 FIELD Connection Exhaust Fan DSP 640 BLK A B BPS_S 617 BRN 6 5 638 BRN 638 BRN 627 ORN 628 BLU 629 BRN 603 RED 606 BRN 639 RED 607 RED 609 RED 611 RED 613 RED FIELD A...