background image

4

The mixed/return air sensor (MA_RA) is an air temperature

sensor located in the unit between economizer coil and

evaporator.

The entering water temperature sensor (EWT) is a probe

type sensor inserted into a copper stub at the unit water inlet

connection.

The 50XJ units can be connected to two types of building

water systems: variable and fixed or constant flow control. In

either case, the economizer water valves are opened whenever

there is a call for cooling and the inlet water temperature is cold-

er than the econimizer lockout set point.
Dependencies — Water economizer option is enabled, fan is

on, and inlet water temperature is below set point; or from “re-

mote scheduler,” or from “remote linkage.”

Economizer mode is switched to off or no start if there is no

condenser water flow, fire input is on, fan is not on, or the unit

is in unoccupied mode.
Variable Waterflow Systems — Whenever water economizer

is off, the economizer flow control valve is fully closed and the

reverse flow valve directly to the condenser is fully open. Upon

engagement of the water economizer, the economizer flow con-

trol valve should be controlled to maintain the mixed air temper-

ature as sensed by the MA-RA sensor, located between the

economizer coil and the DX (direct expansion) cooling coil at a

temperature near the supply air set point. The the reverse flow

valve will be controlled in reverse of the economizer flow con-

trol valve’s position. The following formula is an example: re-

verse/head press ctrl output = 100 – two-position/econo output.

When the unit is off, both valves are closed.

Constant Waterflow Systems — Control of the economizer

flow control valve is same as for variable waterflow systems.

Control of the reverse flow control valve position will inversely

track the economizer flow control valve, such that the total sum

of the two valves open positions always equals 100%. The only

difference between the variable waterflow system and the

constant waterflow system is that for the constant flow system

when the unit is off, the economizer valve will be closed and

the reverse flow control valve will be open.
HEATING COILS AND VALVE (PCB1) — Water or steam

heating options are factory installed. The water or steam con-

trol valve should be installed outside the unit.
HEATING - ELECTRIC HEAT (PCB1) — The  controller

provides a 0 to 10 vdc signal to control remote electric heat. A

field-installed step sequencer can be used to convert this signal

in to 2, 4 or more heating stages.
A single controller output is used to drive either a hydronic

heating coil or the electric heat, so without field modifications,

these are mutually exclusive options.
HEAD PRESSURE CONTROL (PCB1)  —   Head  pressure

control is required for unit installations that will experience en-

tering condenser water temperatures of 55 F or lower.
NOTE: Head pressure control is not needed or used in

conjunction with a water economizer. A refrigerant pressure

transducer monitors head pressure on compressor circuit 1,

allowing the unit main controller to regulate water flow rate

in main water line entering the unit (flow to all condensers).

(Water header design to the condensers will be optimized

such as to provide relative flow rates to each condenser

based on its compressor capacity, enabling successful

waterflow control at the main entering pipe.) There are two

possible water valve configurations, as outlined below.

Pressure transducer input is factory installed in the

discharge line of compressor circuit 1. It is provided 5 vdc by

the unit main controller and returns a signal 1 to 5 vdc linearly.

The sensor’s range is 0 to 550 psig.

Water Valve(s) Control

Variable Building Waterflow Systems

 — Variable waterflow

configurations use only one water valve in the main water

supply pipe. The factory-installed valve is a normally open

motorized variable control type. The valve is controlled by a

2 to 10 vdc signal from the main unit controller using the

reverse/head pressure control output, which modulates to

maintain the head pressure set point.

Constant Building Waterflow Systems

 — Constant waterflow

configurations use two (2) water valves, only one of which is in

the main water supply pipe. The second valve is located in a

bypass pipe to the main outlet water pipe branched off of the

supply pipe immediately ahead of the first valve. This valve is

same type, but normally closed and is controlled in unison with

the first valve, but opposite position, such that the total opening

of the 2 valves always equals 100%.
VFD BYPASS (PCB1) — The  variable  frequency  drive

(VFD) bypass option provides backup for the VFD in VAV

units. The bypass includes a control switch to select across-the-

line operation or operation through the VFD. When the bypass

is switched to across-the-line operation, the fan will not start

until the user indicates that the VFD access doors are secure via

the BACview keypad. The controller provides an output to sig-

nal the remote VAV dampers to open fully before the fan is

started at full speed. A duct high static (DHS) switch shuts

down the fan if the duct static exceeds the switch setting.
VENTILATION OUTPUT (PCB2) — The ventilation output

is a controller output signal (available for field connection) to a

field-supplied ventilation damper(s). This signal is activated

whenever the unit is in the occupied mode.
SPACE TEMPERATURE SENSOR (PCB2) — A  field-sup-

plied Carrier space temperature sensor is required to maintain

space temperature in sensor mode.
SUPPLY AIR RESET  — Supply air temperature set point

may be reset using one of several sensors. In the case of multi-

ple sensors and configurations, the precedence of sensor use is

from the top of the list to the bottom:
• EWT (PCB2) — EWT sensor installed, entering water

temperature reset configuration on

• SPT (PCB1) — Space reset configuration on

• MA_RA (PCB2) — Configured for return air sensing
EXHAUST FAN CONTROL OUTPUT (PCB1) — This  out-

put is activated whenever the unit is in the occupied mode. This

is a 0 to10 vdc output that controls based on the building pres-

sure input set point.
CONDENSER WATER PUMP REQUEST (PCB2) — This

relay output (provided for field connection) is used to start/stop

the remote condenser water pump. This output is engaged

when the unit is in cooling mode and the supply fan is operat-

ing. This output is also engaged if the economizer freeze pro-

tection is activated.
WATER TOWER REQUEST (PCB2) — This  relay  output

(provided for field connection) is used to start/stop a remote

water cooling tower. This output is engaged when the unit is in

cooling mode and the supply fan is operating.
PHASE LOSS/REVERSAL PROTECTION SWITCH

(PCB2) — A phase loss/reversal switch may be installed to

detect over/under voltage conditions and phase loss or reversal.

This is a factory-installed option. This switch monitors the unit

power supply leads to detect phase loss or reversal. If the

switch detects improper phasing, an input is sent to the unit

controller, which shuts the unit down. When the switch opens,

the controller outputs are forced off, the alarm output will

close, the red alarm lamp will be lit on the BACview display,

and a system alarm will be generated. Unit reset is automatic

when the voltage and power phases have been restored.
FREEZE THERMOSTAT (FREEZ) (PCB2) — The  economiz-

er freezestat, used in conjunction with an optional water

Summary of Contents for OMNIZONE 50XJ104

Page 1: ...n working on this equipment observe precautions in the literature on tags stickers and labels attached to the equip ment and any other safety precautions that apply Follow all safety codes Wear safety...

Page 2: ...tion Optional and Field Installed Accessory Sensors Devices These units can be ordered with options and ac cessories that add functionality and control These options and accessories are used as descri...

Page 3: ...og 5K Sensor IN 10 W8 Therm Dry Water Econ Freezestat Sensor or Switch FREEZE Analog 10K 2 Sensor or Switch Closure IN 11 IW7 Therm Dry configurable Mixed Return Air Temperature MA_RA Analog 10K 2 Sen...

Page 4: ...signal 1 to 5 vdc linearly The sensor s range is 0 to 550 psig Water Valve s Control Variable Building Waterflow Systems Variable waterflow configurations use only one water valve in the main water su...

Page 5: ...l 16 and the negative to terminal 17 SUPPLY AIR RESET BY SPACE TEMPERATURE Use a 10K type II thermistor sensor installed at the entering water temperature sensor location on PCB2 and configure the uni...

Page 6: ...e for remote annunciation connect wiring to terminal block J10 terminal 18 normally open terminal 17 common and or terminal 16 normally closed J4 9 10 RED BLK RED RED BLK BLK BLK RED BLK RED SENSOR 1...

Page 7: ...t digital input such as duct high limit switch When the jumper is in the top position the input is configured for a voltage input for example a humidity sensor The bottom jumper position is used for m...

Page 8: ...50 60 Hz 20VA 0 83A Use Copper Conductors Only 232 EIA EIA 485 Port 1 Port 2a Therm Dry Unused 5 6 7 8 Network Switches 0 off 1 on MSTP m MSTP s PTP SLTA PlugIn Ethernet 8 7 6 5 Protocol 0 0 0 0 0 0...

Page 9: ...If the standby screen is visible press any key to switch to the HOME menu 2 If another screen is displayed press the HOME to switch to the HOME menu 3 Press the LOGOUT softkey to force the system to...

Page 10: ...ompressor start stop test This is the same test point used to test the VFD bypass Since constant volume units do not have remote VAV termi nals there is no built in delay to allow remote boxes to open...

Page 11: ...es Local schedules are one method of starting and stopping the unit at specified intervals There are four normal schedules that provide day to day opera tion There are twelve holiday schedules that ar...

Page 12: ...ule When an override schedule is active it overrides any nor mal or holiday schedule and forces the unit to occupied mode In the example listed under the holiday schedule assume an override schedule...

Page 13: ...runtime limits or clear the accumulated run times To view run times press the CONFIG softkey on the HOME menu then select the RUNTIME option from the CONFIGURATION menu Use the arrow keys to scroll th...

Page 14: ...entry press EXIT and re start the procedure at Step 6 9905 Motor Nom Volt should equal unit voltage 230V or 460V 9906 Motor Nom Current equal to motor FLA see motor nameplate 9907 Motor Nom Freq alwa...

Page 15: ...elp screens START UP WITH ASSISTANT To start up the VFD with the Start Up Assistant perform the following proce dure 1 Select MENU SOFT KEY 2 The Main menu will be displayed 2 Use the UP or DOWN keys...

Page 16: ...and then press EXIT SOFT KEY 1 to return to main menu NOTE The current parameter value appears above the highlight parameter To view the default parameter value press the UP and DOWN keys simultaneous...

Page 17: ...not be changed 6 Press EXIT SOFT KEY 1 twice to return to the main menu START UP General Complete the start up checklist on page CL 1 before attempting system start up Confirm that compressor suction...

Page 18: ...of these sensors in the custom configuration The following sensors when valid are used for the space tempera ture sensor with the highest precedence at the top of the list Space temperature sensor SPT...

Page 19: ...e 65 F HEAD PRESSURE CONTROL HPC In installations where entering water temperature can fall below 55 F where a water economizer described above is not installed the HPC provides an electronic water fl...

Page 20: ...of each compressor and is set to open at pressures above 570 psig It is wired in the 24 vac control power line of the compressor contactor in series with the LPS and FRZ and disables compressor operat...

Page 21: ...he compres sor and attempt to restart it 15 minutes later assuming there is still a call for cooling On a third failed attempt to run the compressor the compressor will be locked out pending a pow er...

Page 22: ...r control of an air economizer OUTDOOR AIR TEMPERATURE ALARM OAT If an outdoor air temperature sensor is installed and configured an alarm with an ID of oat_alarm will be generated if the temperature...

Page 23: ...ISC1 Disconnect Switch DSP Duct Static Pressure Transducer ECONO Economizer Valve Damper Control EWT Entering Water Temperature Sensor FLTS Filter Status Switch FREEZ Freeze Thermostat Water Economize...

Page 24: ...3 L1 T1 L2 T2 L3 T3 FU10 FU11 FU12 COMP3 151 BLK 157 BLU 154 YEL 150 BLK 156 BLU 153 YEL 149 BLK 155 BLU 152 YEL C3 158 BLK 159 BLK CH3 2 1 3 L2 T2 L3 T3 FU13 FU14 FU15 COMP4 162 BLK 168 BLU 165 YEL 1...

Page 25: ...Z2 409 PNK 408 PNK 407 PNK 406 PNK LPS2 400 BLU 534 BLU HPS1 FRZ1 404 BLU 403 BLU 402 BLU 401 BLU LPS1 TB5 531 BRN 528 BRN 525 BRN 522 BRN 532 BRN 427 BRN 433 BRN 432 BRN 430 BRN 428 BRN 429 BRN 431 B...

Page 26: ...tion PUMP REQUEST FIELD Connection TOWER REQUEST FIELD Connection EXT DEHUMIDIFY Tower Sump Leaving Water 627 ORN 628 BLU 629 BRN FIELD Connection TRMOP FIELD Connection VENTR FIELD Connection TRMCT F...

Page 27: ...701 GRN 630 ORN 631 VIO HRN3 4 3 FIELD Connection Exhaust Fan DSP 640 BLK A B BPS_S 617 BRN 6 5 638 BRN 638 BRN 627 ORN 628 BLU 629 BRN 603 RED 606 BRN 639 RED 607 RED 609 RED 611 RED 613 RED FIELD A...

Page 28: ......

Page 29: ......

Page 30: ...right to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500117 01 Printed in U S A Form 50XJ 2T Pg 30 8 14 Replaces 50XJ 1...

Page 31: ...INPUT POWER PHASE SEQUENCE BEEN CONFIRMED WITH A METER Y N _______ HAS THE FAN AND MOTOR PULLEY BEEN CHECKED FOR PROPER ALIGNMENT AND DOES THE FAN BELT HAVE PROPER TENSION Y N _______ HAS WATER BEEN P...

Page 32: ..._____________________________________________________________________________________________ _______________________________________________________________________________________________ __________...

Reviews: