background image

21

will be lit. An alarm with an ID of "dhs_alarm" will be

generated.
FIRE/SHUTDOWN INPUT (FSD) — This  is  a  normally

closed input, which when opened, all control outputs are im-

mediately turned off, including the fan, the alarm output will

close and the red alarm lamp will be lit. An alarm with an ID of

"fire_alarm" will be generated.
CONDENSER WATER FLOW (CDWF) — This  is  an  op-

tional switch that can be used with the Omnizone™ controller.

A thermal dispersion flow switch detects water flowing past

the sensor element and closes normally open contacts that ener-

gize a relay with normally open contacts to the unit controller.

A configuration set point is used to indicate if this switch is in-

stalled and disable alarms from the flow switch. When the flow

switch is installed, the controller will check for water flow

when flow is requested for unit operation and if flow is not de-

tected, compressor operation will be disabled. The controller

will also test or to see if there is water flow when the unit is not

operating. If there is no flow when the unit is operating or if

there is flow when the unit is not operating, the alarm output

will close and the red alarm lamp will be lit. An alarm with an

ID of "cdwf_alrm" will be generated.
DIRTY FILTERS SWITCH INPUT (DFS) — This  optional

air pressure switch may be factory-installed in the 50XJ unit to

detect the pressure differential pressure across the return air fil-

ters. This switch is normally open, with manually adjustable

setting at the switch between 0.5 and 1.5 in. wg. Upon closure,

controller should wait to assure closure for minimum 1 minute,

and then the alarm output will close and the red alarm lamp

will be lit. An alarm with an ID of "flts_alarm" will be generat-

ed. However, all other unit operation should remain normal.
PHASE LOSS/REVERSAL INPUT (PRM)  —   A  power

monitor may be installed in the unit to detect over-voltage, un-

der-voltage conditions, phase loss and/or phase reversal. Upon

switch closure a pilot relay is engaged and the input to the con-

troller is closed. In adverse power conditions, all controller out-

puts will be forced off, the alarm output will close and the red

alarm lamp will be lit. An alarm with an ID of "prm_alarm"

will be generated.
ECONOMIZER COIL FREEZE PROTECTION — This in-

put can be either a dry contact input or an averaging thermistor

sensor. This protection is installed in the 50XJ unit when the

economizer coil is provided. In the event the freeze protection

switch contacts open or the sensed economizer temperature

falls below 37 F, or the sensed economizer temperature sensor

fails, the ventilation request output will be closed, the pump

output will be closed, the compressor outputs will be opened,

the alarm output will close, the water economizer valve will

open to 100%, and the red alarm lamp will be lit. This will

maintain condenser water flow through the coil to prevent

freezing the coil while stopping all other operations that could

have contributed or will be affected by the freeze condition. An

alarm with an ID of "eco_freeze" will be generated.

If the freeze condition is maintained for 15 minutes, the sup-

ply fan will be stopped. The optional factory-installed switch is

a manually reset device. The optional factory-installed thermis-

tor will automatically reset when the return-air temperature ex-

ceeds 42 F.
COMPRESSOR 

STATUS 

— 

Compressor status is deter-

mined from the compressor relay (CRx) inputs to the control-

ler. If a compressor input is off for several seconds while that

compressor is commanded on, the compressor output will be

shut down. After five minutes, the controller will attempt to re-

start the compressor, provided there is a call for cooling. If the

compressor fails again, the controller will shut down the com-

pressor and attempt to restart it 10 minutes later. If the com-

pressor fails again, the controller will shut down the compres-

sor and attempt to restart it 15 minutes later, assuming there is

still a call for cooling. On a third failed attempt to run the

compressor, the compressor will be locked out pending a pow-

er reset or the end of the cooling cycle (no cooling demand).

When a compressor is locked out or the controller detects

compressor operation with no call for that compressor, the

alarm output will close and the red alarm lamp will be lit. An

alarm with an ID of "dx#_alarm" will be generated, where "#"

designates which compressor (numbers 1 through 4) is locked

out. This alarm is only maintained while the controller is call-

ing for a compressor and compressor operation is not detected

or while compressor operation is detected and the controller is

not calling for operation.

An alarm with ID of "dx#_lockout" is generated when it be-

comes locked out after three run attempts.
SUPPLY FAN STATUS — Supply fan status is determined

by duct static pressure sensor. If the fan is operating and a fan

speed signal is sent to the VFD, the duct static pressure must

become greater than the supply fan proof level (minsps_sp) for

the supply fan status software point to turn on. When the duct

static pressure becomes lower than the supply fan status low set

point, the supply fan status will indicate OFF.
SUPPLY FAN FAILURE (OFF) — If the supply fan status is

off for 4 minutes while the fan output is on, the alarm output

will close and the red alarm lamp will light. An alarm with an

ID of "sf_fail" is generated. This alarm does not directly affect

unit operation; however, the cooling, heating and other outputs

require the fan status to be on before they can be engaged.
SUPPLY FAN FAILURE (ON) — If the supply fan status is

on for 4 minutes while the fan output is off, the alarm output

will close and the red alarm lamp will be lit. An alarm with an

ID of "sfs_alarm" will be generated. This error does not affect

unit operation.
REFRIGERANT  PRESSURE TRANSDUCER (PRES)  — 

If the optional head pressure control option is enabled and the

pressure transducer input exceeds 420 psig or falls below

-6.7 psig, head pressure control will be disabled, the alarm out-

put will close and the red alarm lamp will be lit. An alarm with

an ID of "ref_pres_alarm" will be generated.
INDOOR AIR QUALITY SENSOR ALARM (IAQ) —   If

an indoor air quality sensor is field-installed and configured,

the controller will consider the IAQ input invalid if the level

falls below 0 ppm or exceeds 2000 ppm, then the alarm output

will close and the red alarm lamp will be lit. An alarm with an

ID of "iaq_sns_alarm" will be generated and the control point

will show 0 ppm. This error disables demand ventilation, but

has no other effect on unit operation.
INDOOR RELATIVE HUMIDITY SENSOR ALARM

(IRH) — If an indoor relative humidity sensor is field-installed

and configured, the controller will consider the IRH input in-

valid if the level falls below 0 or exceeds 100 %, then the alarm

output will close and the red alarm lamp will be lit. An alarm

with an ID of "irh_sns_alarm" will be generated and the control

point will show 0% rh. This error disables humidity control,

but has no other effect on unit operation.
SPACE STATIC PRESSURE ALARM (BLDG PRES-

SURE) — If a building pressure sensor is field-installed and

configured, the controller will consider the pressure input in-

valid if the level falls below the configured low range set point

or exceeds the low range set point plus the sensor range. In this

case the alarm output will close and the red alarm lamp will be

lit. An alarm with an ID of "spstatic" will be generated and the

control point will show 0 in. wg. This error disables space

(building) static pressure control, but has no other effect on unit

operation.
SPACE TEMPERATURE SENSOR FAILURE (SPT) — If

a space temperature sensor (SPT) is field-installed and config-

ured, the controller will consider the SPT input invalid if the in-

put temperature falls below 2 F or exceeds 180 F for a continu-

ous 10 seconds, then the alarm output will close and the red

alarm lamp will be lit. An alarm with an ID of "spt_alarm" will

Summary of Contents for OMNIZONE 50XJ104

Page 1: ...n working on this equipment observe precautions in the literature on tags stickers and labels attached to the equip ment and any other safety precautions that apply Follow all safety codes Wear safety...

Page 2: ...tion Optional and Field Installed Accessory Sensors Devices These units can be ordered with options and ac cessories that add functionality and control These options and accessories are used as descri...

Page 3: ...og 5K Sensor IN 10 W8 Therm Dry Water Econ Freezestat Sensor or Switch FREEZE Analog 10K 2 Sensor or Switch Closure IN 11 IW7 Therm Dry configurable Mixed Return Air Temperature MA_RA Analog 10K 2 Sen...

Page 4: ...signal 1 to 5 vdc linearly The sensor s range is 0 to 550 psig Water Valve s Control Variable Building Waterflow Systems Variable waterflow configurations use only one water valve in the main water su...

Page 5: ...l 16 and the negative to terminal 17 SUPPLY AIR RESET BY SPACE TEMPERATURE Use a 10K type II thermistor sensor installed at the entering water temperature sensor location on PCB2 and configure the uni...

Page 6: ...e for remote annunciation connect wiring to terminal block J10 terminal 18 normally open terminal 17 common and or terminal 16 normally closed J4 9 10 RED BLK RED RED BLK BLK BLK RED BLK RED SENSOR 1...

Page 7: ...t digital input such as duct high limit switch When the jumper is in the top position the input is configured for a voltage input for example a humidity sensor The bottom jumper position is used for m...

Page 8: ...50 60 Hz 20VA 0 83A Use Copper Conductors Only 232 EIA EIA 485 Port 1 Port 2a Therm Dry Unused 5 6 7 8 Network Switches 0 off 1 on MSTP m MSTP s PTP SLTA PlugIn Ethernet 8 7 6 5 Protocol 0 0 0 0 0 0...

Page 9: ...If the standby screen is visible press any key to switch to the HOME menu 2 If another screen is displayed press the HOME to switch to the HOME menu 3 Press the LOGOUT softkey to force the system to...

Page 10: ...ompressor start stop test This is the same test point used to test the VFD bypass Since constant volume units do not have remote VAV termi nals there is no built in delay to allow remote boxes to open...

Page 11: ...es Local schedules are one method of starting and stopping the unit at specified intervals There are four normal schedules that provide day to day opera tion There are twelve holiday schedules that ar...

Page 12: ...ule When an override schedule is active it overrides any nor mal or holiday schedule and forces the unit to occupied mode In the example listed under the holiday schedule assume an override schedule...

Page 13: ...runtime limits or clear the accumulated run times To view run times press the CONFIG softkey on the HOME menu then select the RUNTIME option from the CONFIGURATION menu Use the arrow keys to scroll th...

Page 14: ...entry press EXIT and re start the procedure at Step 6 9905 Motor Nom Volt should equal unit voltage 230V or 460V 9906 Motor Nom Current equal to motor FLA see motor nameplate 9907 Motor Nom Freq alwa...

Page 15: ...elp screens START UP WITH ASSISTANT To start up the VFD with the Start Up Assistant perform the following proce dure 1 Select MENU SOFT KEY 2 The Main menu will be displayed 2 Use the UP or DOWN keys...

Page 16: ...and then press EXIT SOFT KEY 1 to return to main menu NOTE The current parameter value appears above the highlight parameter To view the default parameter value press the UP and DOWN keys simultaneous...

Page 17: ...not be changed 6 Press EXIT SOFT KEY 1 twice to return to the main menu START UP General Complete the start up checklist on page CL 1 before attempting system start up Confirm that compressor suction...

Page 18: ...of these sensors in the custom configuration The following sensors when valid are used for the space tempera ture sensor with the highest precedence at the top of the list Space temperature sensor SPT...

Page 19: ...e 65 F HEAD PRESSURE CONTROL HPC In installations where entering water temperature can fall below 55 F where a water economizer described above is not installed the HPC provides an electronic water fl...

Page 20: ...of each compressor and is set to open at pressures above 570 psig It is wired in the 24 vac control power line of the compressor contactor in series with the LPS and FRZ and disables compressor operat...

Page 21: ...he compres sor and attempt to restart it 15 minutes later assuming there is still a call for cooling On a third failed attempt to run the compressor the compressor will be locked out pending a pow er...

Page 22: ...r control of an air economizer OUTDOOR AIR TEMPERATURE ALARM OAT If an outdoor air temperature sensor is installed and configured an alarm with an ID of oat_alarm will be generated if the temperature...

Page 23: ...ISC1 Disconnect Switch DSP Duct Static Pressure Transducer ECONO Economizer Valve Damper Control EWT Entering Water Temperature Sensor FLTS Filter Status Switch FREEZ Freeze Thermostat Water Economize...

Page 24: ...3 L1 T1 L2 T2 L3 T3 FU10 FU11 FU12 COMP3 151 BLK 157 BLU 154 YEL 150 BLK 156 BLU 153 YEL 149 BLK 155 BLU 152 YEL C3 158 BLK 159 BLK CH3 2 1 3 L2 T2 L3 T3 FU13 FU14 FU15 COMP4 162 BLK 168 BLU 165 YEL 1...

Page 25: ...Z2 409 PNK 408 PNK 407 PNK 406 PNK LPS2 400 BLU 534 BLU HPS1 FRZ1 404 BLU 403 BLU 402 BLU 401 BLU LPS1 TB5 531 BRN 528 BRN 525 BRN 522 BRN 532 BRN 427 BRN 433 BRN 432 BRN 430 BRN 428 BRN 429 BRN 431 B...

Page 26: ...tion PUMP REQUEST FIELD Connection TOWER REQUEST FIELD Connection EXT DEHUMIDIFY Tower Sump Leaving Water 627 ORN 628 BLU 629 BRN FIELD Connection TRMOP FIELD Connection VENTR FIELD Connection TRMCT F...

Page 27: ...701 GRN 630 ORN 631 VIO HRN3 4 3 FIELD Connection Exhaust Fan DSP 640 BLK A B BPS_S 617 BRN 6 5 638 BRN 638 BRN 627 ORN 628 BLU 629 BRN 603 RED 606 BRN 639 RED 607 RED 609 RED 611 RED 613 RED FIELD A...

Page 28: ......

Page 29: ......

Page 30: ...right to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500117 01 Printed in U S A Form 50XJ 2T Pg 30 8 14 Replaces 50XJ 1...

Page 31: ...INPUT POWER PHASE SEQUENCE BEEN CONFIRMED WITH A METER Y N _______ HAS THE FAN AND MOTOR PULLEY BEEN CHECKED FOR PROPER ALIGNMENT AND DOES THE FAN BELT HAVE PROPER TENSION Y N _______ HAS WATER BEEN P...

Page 32: ..._____________________________________________________________________________________________ _______________________________________________________________________________________________ __________...

Reviews: