background image

16

The top line of the LCD display shows the basic status

information of the drive. The HAND icon indicates that the

drive control is local from the control panel. The AUTO

icon indicates that the drive control is in remote control

mode through the I/O.

The arrow icon indicates the drive and motor rotation

status. A rotating arrow (clockwise or counterclockwise) in-

dicates that the drive is running. A rotating blinking arrow

indicates that the drive is running but not at set point.

A stationary arrow indicates that the drive is stopped. For

Carrier air handler units, the rotation is always forward.

Using parameter group 34, the middle of the LCD dis-

play can be configured to display 3 parameter values. The

default display shows parameters 0103 (OUTPUT FREQ)

in Hz, 0104 (CURRENT) in amperes, and AI1 (Analog In-

put 1) in revolutions per minute.

The upper right hand corner shows the frequency set

point that the drive will maintain. The bottom corners of the

LCD display show the functions currently assigned to the

two soft keys. The lower middle displays the current time (if

configured to show the time).

The first time the drive is powered up, it is in the OFF

mode. To switch to local hand-held control and control the

drive using the control panel, press the HAND or AUTO

buttons. Pressing the HAND button switches the drive to

hand control while keeping the drive running. Pressing the

AUTO button switches the drive to remote input control.

The OFF button stops the drive. To return to auto control,

press the AUTO button. To start the drive press the HAND

or AUTO button, to stop the drive press the OFF button.

To adjust the speed set point while in HAND mode, press

the UP or DOWN buttons (the reference changes immedi-

ately). The reference can be modified in the local control

(HAND) mode, and can be parameterized (using Group 11

reference select) to also allow modification in the remote

control mode.
Parameters Mode — The Parameters mode is used to

change the parameters on the drive. To change parameters,

perform the following procedure:

1. Select MENU (SOFT KEY 2). The Main menu will be

displayed.

2. Use the UP or DOWN keys to highlight PARAMETERS

on the display screen and press ENTER (SOFT KEY 2).

3. Use the UP or DOWN keys to highlight the desired pa-

rameter group and press SEL (SOFT KEY 2).

4. Use the UP or DOWN keys to highlight the desired pa-

rameters and press EDIT (SOFT KEY 2).

5. Use the UP or DOWN keys to change the value of the

parameters.

6. Press SAVE (SOFT KEY 2) to store the modified value.

Press CANCEL (SOFT KEY 1) to keep the previous val-

ue. Any modifications that are not saved will not be

changed.

7. Choose another parameter or press EXIT (SOFT KEY 1)

to return to the listing of parameter groups. Continue until

all parameters have been configured and then press EXIT

(SOFT KEY 1) to return to main menu.

NOTE: The current parameter value appears above the

highlight parameter. To view the default parameter value,

press the UP and DOWN keys simultaneously. To restore

the default factory settings if a drive fails, download the

parameters to the VFD from the control panel. Parameters

can also be changed individually.
Changed Parameters Mode — The Changed Parameters

mode is used to view and edit recently changed parameters

on the drive. To view the changed parameters, perform the

following procedure:

1. Select MENU (SOFT KEY 2). The Main menu will be

displayed.

2. Use the UP or DOWN keys to highlight CHANGED

PAR on the display screen and press ENTER (SOFT

KEY 2). A list of the recently changed parameters will be

displayed.

3. Use the UP or DOWN keys to highlight the desired pa-

rameter group and press EDIT (SOFT KEY 2) to change

the parameters if desired.

4. Press EXIT (SOFT KEY1) to exit the Changed Parame-

ters mode.

Drive Parameter Backup Mode — The Drive Parameter

Backup mode is used to store the drive parameters. The pa-

rameters can be uploaded from a VFD to the removable

control panel. If a drive failure occurs, the control panel can

then be transferred to the new drive and the parameters

downloaded into memory.

Each drive is custom programmed at the factory. The

first option is to download all parameters. This copies both

application and motor parameters to the drive from the con-

trol panel. This is recommended to create a backup of the

parameters group for the drive.

The second option downloads only the application pa-

rameters to the drive. Parameters 9905, 9906, 9907, 9908,

9909, 1605, 1607, 5201, and group 51 parameters and inter-

nal motor parameters are not copied.
Upload All Parameters — To upload and store all parame-

ters to the control panel from the VFD, perform the follow-

ing procedure:

1. Select MENU (SOFT KEY 2). The Main menu will be

displayed.

2. Use the UP or DOWN keys to highlight PAR BACKUP

on the display screen and press ENTER (SOFT KEY 2).

3. Use the UP or DOWN keys to highlight UPLOAD TO

PANEL and press SEL (SOFT KEY 2).

4. The text “Copying Parameters” will be displayed with a

progress indicator. To stop the process, select ABORT

(SOFT KEY 1).

5. When the upload is complete, the text “Parameter upload

successful” will be displayed.

6. The display will then return to the PAR BACKUP menu.

Select EXIT (SOFT KEY 1) to return to the main menu.

7. The control panel can now be disconnected from the

drive.

Download All Parameters — To download all parameters

from the control panel to the VFD, perform the following

procedure:

1. Install the control panel with the correct parameters onto

the replacement VFD.

2. Select MENU (SOFT KEY 2). The Main menu will be

displayed.

3. Use the UP or DOWN keys to highlight PAR BACKUP

on the display screen and press ENTER (SOFT KEY 2).

4. Use the UP or DOWN keys to highlight DOWNLOAD

TO DRIVE ALL and press SEL (SOFT KEY 2).

MODE

SET POINT

Fig. 9 — Standard Display Example

a39-2919

Summary of Contents for OMNIZONE 50XJ104

Page 1: ...n working on this equipment observe precautions in the literature on tags stickers and labels attached to the equip ment and any other safety precautions that apply Follow all safety codes Wear safety...

Page 2: ...tion Optional and Field Installed Accessory Sensors Devices These units can be ordered with options and ac cessories that add functionality and control These options and accessories are used as descri...

Page 3: ...og 5K Sensor IN 10 W8 Therm Dry Water Econ Freezestat Sensor or Switch FREEZE Analog 10K 2 Sensor or Switch Closure IN 11 IW7 Therm Dry configurable Mixed Return Air Temperature MA_RA Analog 10K 2 Sen...

Page 4: ...signal 1 to 5 vdc linearly The sensor s range is 0 to 550 psig Water Valve s Control Variable Building Waterflow Systems Variable waterflow configurations use only one water valve in the main water su...

Page 5: ...l 16 and the negative to terminal 17 SUPPLY AIR RESET BY SPACE TEMPERATURE Use a 10K type II thermistor sensor installed at the entering water temperature sensor location on PCB2 and configure the uni...

Page 6: ...e for remote annunciation connect wiring to terminal block J10 terminal 18 normally open terminal 17 common and or terminal 16 normally closed J4 9 10 RED BLK RED RED BLK BLK BLK RED BLK RED SENSOR 1...

Page 7: ...t digital input such as duct high limit switch When the jumper is in the top position the input is configured for a voltage input for example a humidity sensor The bottom jumper position is used for m...

Page 8: ...50 60 Hz 20VA 0 83A Use Copper Conductors Only 232 EIA EIA 485 Port 1 Port 2a Therm Dry Unused 5 6 7 8 Network Switches 0 off 1 on MSTP m MSTP s PTP SLTA PlugIn Ethernet 8 7 6 5 Protocol 0 0 0 0 0 0...

Page 9: ...If the standby screen is visible press any key to switch to the HOME menu 2 If another screen is displayed press the HOME to switch to the HOME menu 3 Press the LOGOUT softkey to force the system to...

Page 10: ...ompressor start stop test This is the same test point used to test the VFD bypass Since constant volume units do not have remote VAV termi nals there is no built in delay to allow remote boxes to open...

Page 11: ...es Local schedules are one method of starting and stopping the unit at specified intervals There are four normal schedules that provide day to day opera tion There are twelve holiday schedules that ar...

Page 12: ...ule When an override schedule is active it overrides any nor mal or holiday schedule and forces the unit to occupied mode In the example listed under the holiday schedule assume an override schedule...

Page 13: ...runtime limits or clear the accumulated run times To view run times press the CONFIG softkey on the HOME menu then select the RUNTIME option from the CONFIGURATION menu Use the arrow keys to scroll th...

Page 14: ...entry press EXIT and re start the procedure at Step 6 9905 Motor Nom Volt should equal unit voltage 230V or 460V 9906 Motor Nom Current equal to motor FLA see motor nameplate 9907 Motor Nom Freq alwa...

Page 15: ...elp screens START UP WITH ASSISTANT To start up the VFD with the Start Up Assistant perform the following proce dure 1 Select MENU SOFT KEY 2 The Main menu will be displayed 2 Use the UP or DOWN keys...

Page 16: ...and then press EXIT SOFT KEY 1 to return to main menu NOTE The current parameter value appears above the highlight parameter To view the default parameter value press the UP and DOWN keys simultaneous...

Page 17: ...not be changed 6 Press EXIT SOFT KEY 1 twice to return to the main menu START UP General Complete the start up checklist on page CL 1 before attempting system start up Confirm that compressor suction...

Page 18: ...of these sensors in the custom configuration The following sensors when valid are used for the space tempera ture sensor with the highest precedence at the top of the list Space temperature sensor SPT...

Page 19: ...e 65 F HEAD PRESSURE CONTROL HPC In installations where entering water temperature can fall below 55 F where a water economizer described above is not installed the HPC provides an electronic water fl...

Page 20: ...of each compressor and is set to open at pressures above 570 psig It is wired in the 24 vac control power line of the compressor contactor in series with the LPS and FRZ and disables compressor operat...

Page 21: ...he compres sor and attempt to restart it 15 minutes later assuming there is still a call for cooling On a third failed attempt to run the compressor the compressor will be locked out pending a pow er...

Page 22: ...r control of an air economizer OUTDOOR AIR TEMPERATURE ALARM OAT If an outdoor air temperature sensor is installed and configured an alarm with an ID of oat_alarm will be generated if the temperature...

Page 23: ...ISC1 Disconnect Switch DSP Duct Static Pressure Transducer ECONO Economizer Valve Damper Control EWT Entering Water Temperature Sensor FLTS Filter Status Switch FREEZ Freeze Thermostat Water Economize...

Page 24: ...3 L1 T1 L2 T2 L3 T3 FU10 FU11 FU12 COMP3 151 BLK 157 BLU 154 YEL 150 BLK 156 BLU 153 YEL 149 BLK 155 BLU 152 YEL C3 158 BLK 159 BLK CH3 2 1 3 L2 T2 L3 T3 FU13 FU14 FU15 COMP4 162 BLK 168 BLU 165 YEL 1...

Page 25: ...Z2 409 PNK 408 PNK 407 PNK 406 PNK LPS2 400 BLU 534 BLU HPS1 FRZ1 404 BLU 403 BLU 402 BLU 401 BLU LPS1 TB5 531 BRN 528 BRN 525 BRN 522 BRN 532 BRN 427 BRN 433 BRN 432 BRN 430 BRN 428 BRN 429 BRN 431 B...

Page 26: ...tion PUMP REQUEST FIELD Connection TOWER REQUEST FIELD Connection EXT DEHUMIDIFY Tower Sump Leaving Water 627 ORN 628 BLU 629 BRN FIELD Connection TRMOP FIELD Connection VENTR FIELD Connection TRMCT F...

Page 27: ...701 GRN 630 ORN 631 VIO HRN3 4 3 FIELD Connection Exhaust Fan DSP 640 BLK A B BPS_S 617 BRN 6 5 638 BRN 638 BRN 627 ORN 628 BLU 629 BRN 603 RED 606 BRN 639 RED 607 RED 609 RED 611 RED 613 RED FIELD A...

Page 28: ......

Page 29: ......

Page 30: ...right to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500117 01 Printed in U S A Form 50XJ 2T Pg 30 8 14 Replaces 50XJ 1...

Page 31: ...INPUT POWER PHASE SEQUENCE BEEN CONFIRMED WITH A METER Y N _______ HAS THE FAN AND MOTOR PULLEY BEEN CHECKED FOR PROPER ALIGNMENT AND DOES THE FAN BELT HAVE PROPER TENSION Y N _______ HAS WATER BEEN P...

Page 32: ..._____________________________________________________________________________________________ _______________________________________________________________________________________________ __________...

Reviews: