Table 6 — Unit Status Menu
Set Controller Address —
The UC Open XP control-
ler’s rotary switches determine the UC open XP’s MAC ad-
dress when it is placed on a BACnet MS/TP network. The rota-
ry switches define the MAC address portion of the device’s
BACnet address, which is composed of the network address
and MAC address.
Perform the following procedure to assign an address:
1. Turn off the UPC Open XP power switch.
2. Using the rotary switches, set the controller address. Set
the Tens (10’s) switch to the tens digit of the address, and
set the Ones (1’s) switch to the ones digit. For example, if
the controller address is 25, point the arrow on the 10’s
switch to 2 and the aroow on the 1’s switch to 5. See Fig.
7.
3. Turn on the UPC Open XP power switch. The controller
reads the address each time power is applied.
50XJ Variable Frequency Drive (VFD) Control
and Start-Up —
The VFD is factory-wired and pro-
grammed for proper operation with the unit controls. No instal-
lation or service adjustments are normally required. There is a
keypad/display mounted on the front of the VFD which is inde-
pendent of the main 50XJ control display.
For basic information on using the VFD keypad/display re-
fer to the VFD Control and Display section.
VFD START-UP PROCEDURE — The following procedure
is used to start up the VFD.
1. Switch the 50XJ PCB1 power switch to OFF.
2. Apply VFD unit power. From the VFD keypad, perform
the following steps.
3. Press [EXIT] at the "Auto Choice - Is this an air-handler
or rooftop?" prompt.
4. Press [MENU] until the "Main Menu" is displayed.
5. Use the UP/DOWN keys to select "ASSISTANTS" and
press <ENTER>.
6. Use the UP/DOWN keys to select "Commission Drive"
and press [SEL].
7. Verify the following parameters. If they are correct, press
<SAVE> to move to the next parameter. Use the UP/
DOWN keys to change parameters, then press <SAVE>.
If you make a mistake in the data entry, press <EXIT>
and re-start the procedure at Step 6.
9905 Motor Nom Volt - should equal unit voltage
(230V or 460V)
9906 Motor Nom Current - equal to motor FLA (see
motor nameplate).
9907 Motor Nom Freq - always 60 Hz.
9908 Motor Nom Speed - set to motor nameplate
RPM.
9909 Motor Nom Power - set to motor nameplate HP.
9902 HVAC Default - press <EXIT>
8. Press <EXIT>, <EXIT>.
9. Press [MENU] until the "Main Menu" is displayed.
10. Use the UP/DOWN keys to select "PARAMETERS" and
press <ENTER>.
STATUS POINT
INDICATORS
Operating Mode
OFF
Fan Only
Economizer
DX Cooling
Heating
Test
Shutdown
Alarm Output
Off or On
Occupancy Status
Occupied or Unoccupied
Occupancy Control
Always Occupied
Local Schedule
BACnet Schedule
BAS On/Off
Remote DI
Fire/Shutdown Input
Ok or Alarm
Power Monitor
Ok or Alarm
Fan
Off or On
Fan Output
<value> %
VFD Bypass
Off or On
Duct Static Pressure
<value> in. wg
Duct Hi-Limit Switch
Ok or Alarm
Filter Status Switch
Ok or Alarm
Supply Air Temperature
<value> F
Cooling SAT Setpoint
<value> F
Heating SAT Setpoint
<value> F
External Cooling Reset
<value> vdc
Space Temperature
<value> F
Rnet Sensor
Inactive or Connected
Compressor 1 Status
Off or On
Compressor 2 Status
Off or On
Compressor 3 Status
Off or On
Compressor 4 Status
Off or On
Heating Capacity
<value> %
Condenser Water flow
Flow or No Flow
Refrigerant Pressure
<value> PSIG
Modulating Valve
<value> %
Water Economizer Valve
<value> %
Outdoor Air Damper
<value> %
VAV Terminal Open
Off or On
VAV Terminal Operate
Off or On
Heat Interlock Relay
Off or On
Ventilation Request
Off or On
Water Pump Request
Off or On
Tower Request
Off or On
Entering Water Temp
<value> F
Mixed/Return Air Temp
<value> F
Economizer Input
<value> F
Freeze Stat Input
Ok or Alarm
Outdoor Air Temperature
<value> F
Enthalpy Input
Ok or High
Indoor Air Quality Level
<value> ppm
Indoor Relative Humidity
<value> %
Humidity Output
Off or On
Space Static Pressure
<value> inches w.c.
Exhaust Fan Output
<value> %
Leaving Water Temperature
<value> F
Tower Sump Temperature
<value> F
10'
s
1'
s
1
3
45
2
7
8
9
6
0
1
3
45
2
7
8
9
6
0
Fig. 7 — Address Rotary Switches
a48-8578